Mounting the Receiver
• Select a ceiling or wall position that does not block
reception for the mounting location.
Note that the receiver cord is 2.0 m.
• First, hook the clamps 11 onto the receiver mount 10
as shown in the diagram below, then partially tighten
the mounting screws 12 .
• Fit the receiver 8 into the receiver mount 10 so that
the locking hooks are firmly engaged.
• Fit the above mount into the ceiling or wall opening and
tighten the screws 12
clasp the ceiling or wall materials.
• Attach the receiver cover 9 so that the hooks on the
inside are firmly hooked onto the receiver mount 10 .
• Lead the receiver cord and connect it to the control box.
11.2.4. CONNECTING THE DRAIN PIPING
• Lay the drain piping so as to ensure drainage.
• Use a locally purchased VP20 general rigid PVC pipe (outer diameter ø26) for the drain piping and firmly connect the indoor
unit and the drain piping using PVC adhesive to ensure that no leakage occurs.
• Drain piping located indoor should always be insulated by wrapping with locally purchased insulation (foamed polyethylene with
a thickness of 10 mm or more).
• The drain piping should have a downward gradient (1/ 50 or more) and should be secured by using pipe hanging equipment to
avoid creating hills or traps partway.
• Should there be any obstacle preventing the drain piping from being extended smoothly, the drain piping can be raised outside
of the main unit as shown in the illustration below.
until the clamps 11
CAUTION
Strictly do not install and extend the drain piping from the main unit drain water
outlet horizontally or upward or raised it 20 cm or more. Doing so may result in
poor drainage or drain motor failure.
firmly