Panasonic CU-E18DBE Service Manual page 30

Hide thumbs Also See for CU-E18DBE:
Table of Contents

Advertisement

CS-E15DD3EW CU-E15DBE / CS-E18DD3EW CU-E18DBE
8.2.3.
Protection Control For Heating Operation
8.2.3.1.
Intake Air Temperature Control
Compressor will operate at Max freq 94 (E15D), 128 (E18D) Hz if either one of the below conditions occur:
1. When the indoor intake air temperature is less than 21°C and remote control setting fan speed is lower Me-.
2. When the indoor intake air temperature is 35°C or above.
8.2.3.2.
Outdoor Air Temperature Control
The Max current value is regulated in accordance to the outdoor air temperature as shown in the below figures.
8.2.3.3.
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
30