Appendix 1: - P1 Communications Set-up and Point Map

Parameter Set-up: The Table below lists the Parameters and the setting values required for proper
P1 FLN communication and control
Parameter number/name
P0003: User access level
P2040: CB telegram off time
P2041(index 0): CB parameter
P0918: CB address
P0700 (index 0)
P1000 (index 0)
Point Number
Point
(drive
Type
parameter)
01
LAO
02
LAO
(03)
LAI
(05)
LAI
(06)
LAI
(07)
LAI
(08)
LAI
(09)
LAI
(13)
LAI
(14)
LAI
(16)
LAI
(17)
LAI
20
LAO
(21)
LDI
(22)
LDO
20
Set to 3 to allow access to required parameters.
Set to 0 to tell the drive to start looking for communication via setting of
P2041.
Set to "1 Set to "0" for FLN (P1) control (set to "1" for FLN (N2) control).
Set to "1-99" for addressing of the device.
Set to 6 tells the SED2 to look for a start command from P1 in the auto mode.
Set to 6 tells the SED2 to look for its speed source from P1 in the auto mode.
P1 Point Map
Descriptor
Factory Default
(SI Units)
CTLR ADDRESS
99
APPLICATION
2722
FREQ OUTPUT
0
SPEED
0
CURRENT
0
TORQUE
0
ACTUAL POWER
0
TOTAL KWH
0
DC BUS VOLT
0
REFERENCE
0
RATED PWR
0
OUTPUT VOLTS
0
OVRD TIME
1
FWD.REV
FWD
CMD FWD.REV
FWD
Value
Engr. Units
Slope
(SI Units)
(SI Units)
1
1
HZ
.04
RPM
1
A
0.5
NM
.02
HP/KW
.01
KWH
1
V
1
HZ
.04
HP/KW
.01
V
1
HRS
1
1
1
Intercept
On Text
Off Text
(SI Units)
0
0
-650
-16250
0
-3250
0
0
0
-650
0
0
0
0
REV
REV
0
FWD
FWD