Point Database For Siemens Apogee P1 - Siemens Apogee P1 Technical Manual

Communications option
Hide thumbs Also See for Apogee P1:
Table of Contents

Advertisement

Point
Point
Subpoint Name
Number
Type
1
LAO
CTRL ADDRESS
2
LAO
3
LAI
4
LAI
5
LAI
6
LAI
7
LAI
8
LAI
10
LAI
12
LAI
13
LAI
14
LAI
20
LAO
21
LDI
22
LDO
23
LDI
24
LDO
25
LAO
27
LDO
28
LDO
29
LDO
30
LAO
31
LAO
32
LAO
33
LAO
34
LAO
35
LDO
37
LAO
40
LDI
41
LDI
42
LDI
44
LDO
45
LDI
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
Siemens APOGEE P1 Communications Interface

Point Database for Siemens APOGEE P1

Factory Default
(SI Units)
ED_HVAC10
Freq Output
Freq Demand
Speed
Current
Torque
Power
Drive KWH
Runtime
DC Bus Volts
Output Volts
OVRD Time
Direction
FWD
Direction SP
FWD
RUN
STOP
RUN SP
STOP
Stop Mode
Coast Stop
FALSE
Fast Stop
FALSE
Day.Night
Curr Limit
150.0
Accel Time 1
Decel Time 1
Stop Decel T
Fast Decel T
Run Enable
ENABLE
Reference SP
O/P Relay 1
O/P Relay 2
O/P Relay 3
Flycatch EN
FALSE
Flycatching
FALSE
Engr. Units
(SI Units)
1
2731
0
Hz
0
Hz
0
RPM
0
A
0
PCT
0
Kw
0
KWh
0
Hrs
0
Volts
0
Volts
0
DAY
PCT
10.0
SECS
10.0
SECS
10.0
SECS
0.1
SECS
0
PCT
OFF
OFF
OFF
Slope
Intercept
On Text
(SI Units)
(SI Units)
1
0
1
0
0.1
0
0.1
0
0.1
0
0.1
-1638.3
0.1
-1638.3
0.1
0
0.1
0
1
0
1
0
1
0
1
0
REV
1
0
REV
1
0
RUN
1
0
RUN
1
0
1
0
TRUE
1
0
TRUE
1
0
0.1
0
0.1
0
0.1
0
0.1
0
0.1
0
1
0
ENABLE
0.1
-1683.3
1
0
ON
1
0
ON
1
0
ON
1
0
TRUE
1
0
TRUE
continued on next page...
11
Off Text
FWD
FWD
STOP
STOP
FALSE
FALSE
DISABL
OFF
OFF
OFF
FALSE
FALSE

Advertisement