GE Simon XTi Installation Manual page 11

Hide thumbs Also See for Simon XTi:
Table of Contents

Advertisement

Household fire warning system (UL 985), basic system plus the
following:
Wireless smoke sensor 60-848-02-95, TX-6010-01-1
learned into sensor group 26.
Panel piezo beeps turned on
Control panel alarms set to on
Siren timeout set to 4 minutes or more
Trouble beeps set to on
RF jam detect set to on
Hardwired siren supervision set to on
Smoke supervision set to on
UL 1635 digital alarm communicator system the following
settings are required only if the system is set up for central
station reporting:
Phone mode 1 set to "All SIA" or "All CID"
Automatic phone test set to 001
RF timeout set to 4 hours
AC power failure report set to on
CPU low battery report set to on
Fail to communicate set to on
Entry delay plus the dialer delay must not exceed 60
seconds
SIA system requirements
Verified to SIA CP-01-2007 by ETL, basic system, plus if
multiple annunciations are required, use hardwired siren 13-
046.
Note:
For UL 1635 installations, entry delay plus dialer abort
delay must not exceed 60 seconds.
Table 8 below describes programming requirements to meet
ANSI-SIA CP-01.
Table 8: SIA setting requirements
Function
Default setting
Entry delay
30 seconds
Exit delay
60 seconds
Dialer delay
30 seconds
Auto arm
On
Un-vacated premises
On
Call waiting
Off
Alarm cancel window
6 minutes
System test
Enabled
Communication test
Enabled
Exit extension
On
Swinger shutdown
On (one trip)
Simon® XTi Installation Guide
Function
Fire alarm verify
Duress/panic code
Cross zone
Table 9 below describes nonprogrammable (hard-coded)
system operation, as required to meet ANSI-SIA CP-01.
Table 9: Nonprogrammable system operation
Function
Silent exit
Remote arming exit time and
progress annunciation
Abort annunciation
Cancel report annunciation
Recent closing
Exit error
Restoration of power
Cancel alarm
Central station reporting
Note: The panel shall not be set or programmed to place a call
to a police station number that has not been specifically
assigned by that police station for such service.
successful connection to the central station may be prevented.
Required setting
ATTENTION: Si l'appel en attente est utilisé sur une ligne
d'attente non - appel, connexion réussie à la station centrale
30 to 240 seconds
peut être empêché .
45 to 240 seconds
15 to 45 seconds
The panel has been tested with the following central station
On
receivers using SIA and Contact ID reporting formats:
On
Before beginning installation, installers must verify that the
On if reporting to
central station and
central station is equipped with the following receivers:
customer has call
waiting service
6 to 255 minutes, Off
Enabled
Enabled
On
On (one trip)
Default setting
Off
Disabled
Disabled
CAUTION:
If call waiting is used on a non-call waiting line,
Radionics D6600 central station receiver
Sur-Gard central station receiver with models SG-DRL2A
and SG-CPM2
CS5000 digital alarm communicator receiver
Required setting
On
Disabled
Disabled for zones
with high probability of
false alarms
Operation
All annunciators enabled
All annunciators enabled
Enabled
Enabled
Enabled (2-minute window)
Enabled
Panel resumes operation in same
arming state and disregards alarm
signals from sensors for the first
60 seconds after power
restoration
Enter code only
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents