CHAPTER 5: SETTINGS

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1
These settings specify how the direct input information is processed.
— This setting allows the user to assign a descriptive name to the direct input.
DIRECT INPUT 1 NAME
— Represents the source of direct input 1. The specified direct input is driven by the device
DIRECT INPUT 1 DEVICE ID
identified here.
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
On — Defaults the input to Logic 1
Off — Defaults the input to Logic 0
Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
5.9.6.2 Direct outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT OUTPUTS  DIRECT OUTPUT 1(32)
 DIRECT OUTPUT 1
— This setting allows the user to assign a descriptive name to the direct output.
DIRECT OUT 1 NAME
— This sets the FlexLogic operand that determines the state of this direct output.
DIR OUT 1 OPERAND
5.9.6.3 Application examples
The examples introduced in the earlier Direct Inputs and Outputs section (part of the Product Setup section) are continued
here to illustrate usage of the direct inputs and outputs.
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 1
DIRECT INPUT 1
BIT NUMBER: 1
DIRECT INPUT 1
DEFAULT STATE: Off
DIRECT INPUT 1
EVENTS: Disabled
. This corresponds to the direct output number of the sending device.
— Represents the state of the direct input when the associated direct device is offline. The
DIRECT OUT 1 NAME:
Dir Out 1
DIRECT OUT 1 OPERAND:
Off
DIRECT OUTPUT 1
EVENTS: Disabled
Range: up to 12 alphanumeric characters
Range: 1 to 16
Range: 1 to 32
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
Range: up to 12 alphanumeric characters
Range: FlexLogic operand
Range: Enabled, Disabled