CHAPTER 5: SETTINGS
ANALOG IN 1 MAX
Range: -1000000000.000 to 1000000000.000 in steps of 0.001
Default: 0.000
This setting specifies the "max." value used in deadband calculations. The scaling of this setting is the same as used by
<LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of
the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible
floating point number.
5.3.4.13 Web server HTTP protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  WEB SERVER HTTP PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
The F35 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the F35 "Main Menu." Web pages are available showing DNP and IEC
60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the F35 and a computer to
an Ethernet network, then enter the IP address of the F35 Ethernet port in a web browser.
To close the port, set the port number to 0. The change takes effect when the F35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
5.3.4.14 TFTP protocol
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  TFTP PROTOCOL
 TFTP PROTOCOL
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
HTTP TCP PORT
NUMBER: 80
Figure 5-30: Example of UR web page showing event records
TFTP MAIN UDP PORT
NUMBER: 69
TFTP DATA UDP PORT 1
NUMBER: 0
TFTP DATA UDP PORT 2
NUMBER: 0
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
PRODUCT SETUP