SYSTEM SETUP
BREAKER 1 A/3P OPND
a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted
signal can be used.
BREAKER 1 B CLOSED
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER 1 B OPENED
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER 1 C CLOSED
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1 C OPENED
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER 1 Toperate
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS
BREAKER 1 EXT ALARM
reporting contact.
BREAKER 1 ALARM DELAY
pole position tracking operands does not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
MANUAL CLOSE RECAL1 TIME
operator has initiated a manual close command to operate a circuit breaker.
BREAKER 1 OUT OF SV
5
5-122
— Selects an operand, usually a contact input, that is a normally-closed 52/b status input to create
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— This setting specifies the required interval to overcome transient disagreement between the 52/a
FlexLogic operand is asserted from alarm or blocking purposes.
— This setting selects an operand, usually an external contact input, connected to a breaker alarm
— This setting specifies the delay interval during which a disagreement of status among the three-
— This setting specifies the interval required to maintain setting changes in effect after an
— Selects an operand indicating that breaker 1 is out-of-service.
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
status
BREAKER 1 CLOSED