Selection Of Installation Place; Installation Space; Advice - Toshiba RAV-SM304MUT-E Installation Manual

Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
3

Selection of installation place

WARNING
• Install the air conditioner securely in a location where the base can sustain the weight adequately.
If the strength is not enough, the unit may fall down resulting in injury.
• Install the air conditioner at a height 2.5 m or more from the floor.
If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you
may contact with revolving fan or active electricity.
CAUTION
• Do not install in a location where flammable gas may leaks are possible.
If the gas leak and accumulate around the unit, it may ignite and cause a fire.
Upon approval of the customer, install the air conditioner in a place that satisfies the following
conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot
spring).
(The unit should be used in these places, special protective measures are needed.)
• A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the heat
exchanger and resin part (turbo fan) in the indoor unit may reduce the performance, generate mist or dew drop,
or deform or damage resin parts.)
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior
of the air conditioner, it may spontaneously combust and start a fire.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbour house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted.
(When the outdoor unit is installed on the boundary with the neighbour, pay due attention to the level of noise.)
• Place with poor ventilation. (Before air duct work, check whether value of fan speed, static pressure and duct
resistance are correct.)
• Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art objects,
or where breeding animals or growing plants are kept. (This may degrade the quality of preserved materials.)
• Place where any of high-frequency appliances (including inverter devices, private power generators, medical
equipment, and communication equipment) and inverter-type fluorescent light is installed.
(A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances / equipment
may occur.)
• When the wireless remote controller is used in a room equipped with an inverter-type fluorescent light or at a
place exposed to direct sunlight, signals from the remote controller may not be received correctly.
• Place where organic solvent is used.
• Place near a door or window exposed to humid outside air (Dew drop may form.).
• Place where special spray is used frequently.
9-EN
– 5 –
 Installation space
Ensure there is sufficient space to install the unit and to perform maintenance work as and when required. Keep
15 mm or more for clearance between top plate of the indoor unit and the ceiling surface.
1000 or more
Obstacle
 Selection of installation place
Continual operation of the indoor unit under high-humidity conditions as described below, dew may condense and
water may drop.
Especially, high-humidity atmosphere (dew point temperature: 23 °C or more) may generate dew inside the ceiling.
1. Unit is installed inside the ceiling with slated roof.
2. Unit is installed at a location using inside of the ceiling as fresh air take-in path.
3. Kitchen

Advice

• Set a service check opening panel at right side of the unit (size: 450 × 450 mm or more) for piping, maintenance,
and servicing.
• If installing a unit at such place, put insulating material (such as glass wool) additionally on all the positions of
the indoor unit which come to contact with high-humidity atmosphere.
REQUIREMENT
When the humidity inside the ceiling seems to be higher than 80 %, attach a heat insulator to the side (top)
surface of the indoor unit. (Use a heat insulator that is 10 mm or more thick.)
unit: mm
1000 or more
10-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm404mut-eRav-sm454mut-eRav-sm564mut-e

Table of Contents