Troubleshooting - EBARA DVSU Operating Instructions, Installation & Maintenance Manual

Submersible semi-vortex sewage pump

Advertisement

EBARA Submersible Semi-vortex Sewage Pumps
Operating, Installation, and Maintenance

Troubleshooting

All service should be done by factory trained or qualified personnel only.
Trouble
Cause
Does not start.
(1) Power failure
Starts, but
(2) Large discrepancy between power source and voltage
immediately stops.
(3) Significant drop in voltage
(4) Motor phase malfunction
(5) Electric circuit connection faulty
(6) Faulty connection of control circuit
(7) Blown fuse
(8) Faulty magnetic switch
(9) Water is not at level indicated by float
(10) Float is not in appropriate level
(11) Float defective
(12) Short circuit breaker is functioning
(13) Foreign matter clogging pump
(14) Motor burned out
(15) Motor bearing broken
Operates, but stops
(1) Prolonged dry operation has activated motor protector (1) Raise stop water level
after a while.
and caused pump to stop
(2) High liquid temperature has activated motor protector (2) Lower liquid temperature
and caused pump to stop
Does not pump.
(1) Reverse rotation
Inadequate volume.
(2) Significant drop in voltage
(3) Operating a 60Hz pump on 50Hz
(4) Discharge head is high
(5) Large piping loss
(6) Low operating water level causes air suction
(7) Leaking from discharge piping
(8) Clogging of discharge piping
(9) Foreign Matter in suction inlet
(10) Foreign matter clogging pump
(11) Worn impeller
Over current
(1) Unbalanced current and voltage
(2) Significant voltage drop
(3) Motor phase malfunction
(4) Operating 50HZ pump on 60Hz
(5) Reverse rotation
(6) Low head; excessive volume of water
(7) Foreign matter clogging pump
(8) Motor bearing is worn or damaged
Pump vibrates;
(1) Reverse rotation
excessive operating
(2) Pump clogged with foreign matter
noise.
(3) Piping resonates
(4) Gate valve is closed too far
Single phase motor:
(1) Defective start capacitor
Motor hums, but will not
(2) Defective relay:
run, over load trips.
a) Check relay coil with continuity meter
In approximately 15-20
b) Check for loose or broken connection in relay and
seconds. After an off
start capacitor circuit
time of 30-60 seconds,
c) If after step (2b) motor fails to start, check with
overload protector will
continuity indicator across terminal 162
reclose. If motor again
(3) Defective motor; if motor fails to start after replacing
hums and overload trips,
relay (start or run capacitor if used), motor may be
the fault is probably due to defective
either a defective start
capacitor or relay, or
perhaps the motor itself.
CALL 1-800-577-8111 FOR SALES AND SUPPORT
CAUTION
Remedy
(1)-(3) Contact electric power company; devise counter-measures
(4) Inspect connections and magnetic switch
(5) Inspect electric circuit
(6) Correct wiring
(7) Replace with correct type of fuse
(8) Replace with correct type of magnetic switch
(9) Raise water level
(10) Move float to an appropriate starting level
(11) Repair or replace
(12) Repair location of short circuit
(13) Remove foreign matter
(14) Repair or replace
(15) Repair or replace
(1) Correct rotation (see Operation 2, (3))
(2) Contact electric power company and devise
counter-measures
(3) Check nameplate
(4) Recalculate and adjust
(5) Recalculate and adjust
(6) Raise water level or lower pump
(7) Inspect, repair
(8) Remove foreign matter
(9) Remove foreign matter
(10) Disassemble and remove foreign matter
(11) Replace impeller
(1) Contact electric power company and devise counter-measure
(2) Contact electric power company and devise counter-measure
(3) Inspect connections and magnetic switch
(4) Check nameplate
(5) Correct rotation (see Operation 2)
(6) Replace pump with low head pump
(7) Disassemble and remove foreign matter
(8) Replace bearing
(1) Correct rotation
(2) Disassemble and remove foreign matter
(3) Improve piping
(4) Open gate valve
(1) Replace start capacitor.
(2a) Replace relay if open coil is found
(2b) If circuit is intact, replace start capacitor and restart motor
(2c) If no continuity is indicated, replace relay
(3) Check motor for electrical and mechanical defects
DVSU/DVSHU