Chapter 4
Technical Specifications
Section 4.3

Fiber Optic Ethernet Port Specifications

The following details the specifications for fiber Ethernet ports that can be ordered with the RS930W.
NOTE
Order codes are contained within each product when assembled and configured at the factory. Refer to
the ROS User Guide for the RS930W for information on how to obtain the factory configuration data.
NOTE
• All optical power numbers are listed as dBm averages. To convert from average to peak add 3 dBm.
To convert from peak to average, subtract 3 dBm.
• Maximum segment length is greatly dependent on factors such as fiber quality, and the number
of patches and splices. Consult a Siemens sales associate when determining maximum segment
distances.
Order
Mode
Code
FX01
MM
FX02
MM
FX03
MM
FX04
SM
FX05
SM
FX06
SM
FX07
SM
FX08
SM
FX09
SM
FX10
SM
FX11
MM
Section 4.4

Wireless Ethernet Port Specifications

The following sections detail specifications for wireless Ethernet ports that can be equipped on the RS930W:
Section 4.4.1, "Supported Wireless Standards"
Section 4.4.2, "Radio Characteristics"
Section 4.4.3, "Channel Allocations for IEEE 802.11b/g"
20
Cable
Tx λ
Connector
Type
(typ.)
Type
(μm)
(nm)
62.5/125
ST
1300
50/125
62.5/125
SC
1300
50/125
MTRJ
62.5/125
1300
ST
9/125
1300
SC
9/125
1300
LC
9/125
1300
SC
9/125
1300
LC
9/125
1300
SC
9/125
1300
LC
9/125
1300
LC
50/125
1300
Rx
Tx min.
Tx max.
Sensitivity
(dBm)
(dBm)
(dBm)
-19
-14
-31
-22.5
-19
-14
-31
-22.5
-19
-14
-31
-15
-8
-32
-15
-8
-31
-15
-8
-34
-5
0
-34
-5
0
-35
0
5
-37
0
5
-37
-22.5
-14
-31
RUGGEDCOM RS930W
Installation Guide
Rx
Distance
Saturation
(typ.)
(dBm)
(km)
-14
2
-14
2
-14
2
-3
20
-7
20
-7
20
-3
50
3
50
0
90
0
90
-14
2
Fiber Optic Ethernet Port Specifications
Power
Budget
(dB)
12
8.5
12
8.5
12
17
16
19
29
30
37
37
8.5