NOTE: The static pressure check occurs only at initial installation,
or when INSTALL is run in the INSTALL/SERVICE menu.
Duct Assessment
The following screen will appear after STATIC PRESSURE screen
is exited. Press right- -side button to start Duct Assessment. Duct
Assessment will measure the relative size of the ductwork, up
and through the dampers. These measurements are used to control
the correct amount of airflow in the zoned system. Status messages
will appear on the screen to indicate what the system is doing. The
process will take approximately one minute per zone. The duct
assessment will override a call for heat or cool.
A duct assessment will automatically occur each day at a user
selectable time. The factory default time is 1:00 p.m. but, may be
changed by entering the Zoning Setup menu. See Zoning Setup
section of this manual. The duct assessment will override a call for
heat or cool. The system will first open all zones and drive the
blower to 175 CFM/ton of cooling (or the minimum indoor unit's
airflow, whichever is greater). It will then take a static pressure
measurement. The system will then close all zones and open one
zone at a time, taking a static pressure measurement for each zone.
The system will then close all zones and take a pressure
measurement, getting a value for the duct leakage up to and
through the dampers. With these static pressure measurements, the
system will calculate the relative size of each zone as well as the
percent leakage through the dampers At the end of the process, the
display will show the relative size of each zone duct. See Fig. 23.
If the User Interface detects an error (damper not moving or
damper wired backwards), it will perform the duct assessment
again. If it still detects a damper problem, it will default the
measurements into equal sizes, with 10% leakage, and display the
zone number for the suspected zone damper.
DUCT ASSESSMENT
DUCT ASSESSMENT
MEASURE DUCT
ASSESSMENT ACTIVE
CAPACITY FOR EACH
PLEASE WAIT
OPENING ALL ZONES
ZONE.
AIRFLOW STABILIZING
4 MINUTES ARE REQUIRED
PROGRESS
TO COMPLETE
PRESS START TO BEGIN
QUIT
START
STOP
Fig. 23 - - Duct Assessment
QUICK START
For first time installers, Quick Start will allow a quick start up of
the Infinity Zone System before learning all the details of system
operation. However, for the best possible comfort and operation
refer to the Infinity Zone Control Owner's Manual.
Set Day, Time & Desired Humidity
1. Open the door of the Infinity Zone Control and press the
BASIC button.
2. Adjust the highlighted HOUR setting using the LEFT Up/
Down button.
3. Press SCROLL button (down) to highlight MINUTE.
4. Adjust the MINUTE setting using the LEFT Up/Down
button.
5. Press SCROLL button (down) to highlight DAY.
6. Adjust the current DAY setting using the LEFT Up/Down
button.
7. Press SCROLL button (down) to highlight HUMIDITY.
8. Press the red HEAT button to select heating humidity.
9. Adjust desired heating humidity level using either (+/- -) but-
ton.
to
Override Heating Schedule
NOTE: Override time will not appear if programming has been
turned off.
Quick Program Schedule For All Days
This section will give you a quick program schedule for ALL
DAYS of the week. For more information on how to create
customized schedules for every day, the entire week, or weekend,
refer to the Owner's Manual.
DUCT ASSESSMENT
ZONE
CAPACITY
ZONE1
25
ZONE 2
20
ZONE 3
25
ZONE 4
20
DAMPER LEAKAGE 10
QUIT
START
A04085
The "INSTALL / SERVICE" menus contain a set of vital
information. This information enables the Installer or Service
person to view a summary of what has been installed, etc. This
information is not covered in the Owner's Manual.
To enter INSTALL / SERVICE menus, press and hold the
ADVANCED button for at least ten seconds. The following menu
will appear (See Fig. 24):
8
10. Press the blue COOL button to select cooling humidity.
11. Adjust the desired cooling humidity level using ei-
ther(+/- -)button.
12. To exit press BASIC button or close door.
13. If changes are made, you will be asked to "SAVE
CHANGES? YES/NO."
1. Press the red HEAT button. Heating mode is confirmed
when the red LED next to the red HEAT button is lit.
2. Use the RIGHT Up/Down button to select your desired
heating temperature.
3. The default time for temporarily overriding the temperature
schedule is 2:00 HRS as indicated by the text on the lower
left.
4. You can change the temporary override time in 15- -minute
increments by pressing the LEFT Up/Down button until
the desired override time is selected, or press the HOLD
button anytime to override the schedule indefinitely.
1. Open the door of the control.
2. Press the SCHEDULE button, which allows you to create
one schedule for the entire home.
3. Press either the LEFT or RIGHT side button repeatedly (if
necessary) until "ALLDAYS" is displayed. The WAKE
time period will be highlighted.
4. Using the LEFT Up/Down button, set the start time for this
time period.
5. Press the red HEAT button. Heating temperature will begin
flashing.
6. Set the heating temperature using the RIGHT Up/Down
button.
7. Press the blue COOL button. Cooling temperature will be-
gin flashing.
8. Set the cooling temperature using the RIGHT Up/Down
button.
9. Set the remaining periods by using the SCROLL button to
select "DAY", "EVENING", and "SLEEP".
10. To copy a zone, use SCROLL button to select "COPY".
Select YES and copy this zone schedule to other zones us-
ing NO or YES.
11. Exit the scheduling mode by either closing the door or
pressing the SCHEDULE button.
12. If changes are made, you will be asked to "SAVE
CHANGES YES/NO."
INSTALL / SERVICE MENUS