SYSTEM MALFUNCTION SCREEN

OUTSIDE: 84_ | FAN: AUTO
1--- 800--- 555--- 1212
SYSTEM MALFUNCTION
Fig. 36 - - System Malfunction Screen
Fan Coil
The code number represents flash code on circuit board of fan coil.
Certain faults will generate a system malfunction message on the
main screen. When this occurs, a technician should proceed to the
Last 10 System Events screen in the Service Menu to determine
which fault has caused the message.
Below is a list of which faults will result in a System Malfunction
event:
Code 37 - - Heater output sensed On when not energized
Code 41 - - Blower Motor Fault (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 44 - - Motor Communication Fault (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 45 - - Control failure
Furnace
The code number represents flash code on circuit board of furnace.
Code 13 - - Limit Circuit Lockout
Code 14 - - Ignition Lockout
Code 15 - - Blower Motor Lockout (ventilator, humidifier,
dehumidifier, outdoor unit will be turned off)
Code 21 - - Gas Heating Lockout
Code 22 - - Abnormal Flame Proving Signal
Code 23 - - Pressure Switch Did Not Open
Code 24 - - Secondary Voltage Fuse Open
Code 33 - - Limit Circuit Fault AND high heat only is active
Code 41 - - Blower Motor Fault (cooling mode only) (ventilator,
humidifier, dehumidifier, outdoor unit will be turned off)
Code 45 - - Control Circuitry Lockout
NOTE: For codes 13, 14 and 21, the system will use heat pump
heating exclusively if available. When the error code is cleared or
disappears, furnace heating will resume if still requested.
Service Tool Mode
The - -V model of user interface software version 21 can be used as
a service tool on any Infinity system. Attach the - -V model user
interface anywhere on the ABCD wiring (e.g. at the indoor or
outdoor unit). When the user interface powers up, it will ask the
user if they wish to enter service mode. Selecting "Yes" will allow
the - -V model user interface to take over as the system controller,
putting the regular system user interface to sleep. The screen on
the regular user interface will display "IN SERVICE MODE". The
- -V model user interface will then learn all equipment and function
as the system controller. While in service mode, the - -V model user
Copyright 2011 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
71_
HVAC SERVICE
CALL TECHNICIAON
interface will not transfer any settings or information to or from the
regular user interface- -- -it only takes over control of the system.
After removing the - -V model user interface from the ABCD
wiring, the regular user interface will take over the system after two
minutes.
Outdoor Unit
The code number represents flash code on circuit board of outdoor
unit.
Code 45 - - Control Failure
Code 48 - - Loss of inverter communications
Code 47 - - No 230V at unit
A07036
Code 69 - - Inverter internal fault
Code 73 - - Contactor shorted
Code 74 - - No high voltage at compressor
Code 76 - - Low stage didn't start three times
Code 78 - - High stage didn't start three times
Code 79 - - Run capacitor failed
Code 81 - - Thermal lockout in low stage - - 4 hrs.
Code 82 - - Thermal lockout in high stage - - 4 hrs.
Code 83 - - Low Pressure Lockout - - 4 hrs.
Code 84 - - High Pressure Lockout - - 4 hrs.
Code 85 - - Low contactor open
Code 86 - - Low contactor shorted
Code 87 - - High contactor open
Code 88 - - Inverter Temp Lockout or High Contactor Shorted
Code 89 - - Start Capacitor / Relay Failed
Code 96 - - VDC under voltage lockout
Code 97 - - VDC over voltage lockout
Code 99 - - High torque lockout
User Interface
S Temp sensor failed, loss of communication with smart sensor,
smart sensor fault. "NO SENSOR DATA" shown
S Indoor unit communication fault
S Outdoor unit communication fault
S Packaged product communication fault
S NIM communication fault
S SAM communication fault
S Possible Frozen Coil
S High Room Temp Alert, when 100_F (38_C) exists for at least
10 minutes, and removed when less than or equal to 98_F
(37_C) exists
S Low Room Temp Alert, when 38_F (3_C)exists for at least 10
minutes, and removed when greater than or equal to 40_F (4_C)
exists
S High Humidity Alert, when 80% Rh exists for 30 minutes, and
removed when less than or equal to 78% Rh exists
The user can press the right side button to dismiss the notice. The
regular run mode screen will then appear except "SYSTEM
MALFUNCTION" will appear in place of the day/time. If the error
has not disappeared within 24 hours, the above display will return.
If the error code disappears, "SYSTEM MALFUNCTION" will
disappear and the day/time will reappear.