Heating Circuit 1, Heating Circuit 2, Heating Circuit 3/Group "5 - Viessmann VITODENS 222-F Installation And Service Instructions Manual

Gas condensing storage combi boiler
Table of Contents

Advertisement

DHW/group "3"
Coding in the delivered condition
1: Viessmann diverter
valve
2: Wilo diverter valve
3: Grundfos diverter valve
6C:100
Set speed, internal circu-
lation pump with DHW
heating 100 %
6F:...
Maximum output for
DHW heating in %, speci-
fied by the boiler coding
card
71:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
73:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)

Heating circuit 1, heating circuit 2, heating circuit 3/group "5"

Select "Heating circuit ..." for weather-compensated control units (see page 74).
Select "5" for constant temperature control units (see page 74).
(cont.)
Possible change
6C:0
Set speed adjustable from
to
0 to 100 %
6C:100
6F:0
Max. output for DHW heat-
to
ing adjustable from min.
6F:100
output to 100 %
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value
73:1
"ON" from once per hour
to
for 5 min up to 6 times per
73:6
hour for 5 min during the
time program
73:7
Constantly "ON"
Code 2