Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
Eb
X
EC
X
Ed
X
114
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
Cause
Measures
Repeated
Check gap
flame loss
between ionisation
during cali-
electrode and
bration
burner gauze
assembly (see
page 38).
Check allocation of
gas type (see
page 30).
Check flue system;
remedy flue gas
recirculation if
required.
Press reset button
R.
Parameter
Press reset button
fault during
R
calibration
or
Replace boiler cod-
ing card and press
reset button R.
Internal fault
Replace control
unit.