Viessmann VITODENS 222-F Installation And Service Instructions Manual page 109

Gas condensing storage combi boiler
Table of Contents

Advertisement

Fault codes
(cont.)
Dis-
Const.
played
fault
code
C4
X
C5
X
C6
C7
X
C8
Cd
X
Weath.-
System char-
comp.
acteristics
X
Control mode
X
Control mode,
max. pump
speed
X
Control mode,
max. pump
speed
X
Control mode,
max. pump
speed
X
Control mode,
max. pump
speed
X
Control mode
Troubleshooting
Cause
Measures
Communica-
Check Open
tion error,
Therm extension
Open Therm
extension
Communica-
Check setting of
tion error, var-
coding address
iable speed
"30"
internal pump
Communica-
Check setting of
tion error,
coding address
external vari-
"E5"
able speed
heating circuit
pump, heat-
ing circuit 2
(with mixer)
Communica-
Check setting of
tion error,
coding address
external vari-
"E5"
able speed
heating circuit
pump, heat-
ing circuit 1
(without
mixer)
Communica-
Check setting of
tion error,
coding address
external vari-
"E5"
able speed
heating circuit
pump, heat-
ing circuit 3
(with mixer)
Communica-
Check connec-
tion error,
tions, Vitocom 100
Vitocom 100
and coding
(KM BUS)
address "95"
109