Flexnet Dc Measurements - Outback Power Systems FLEXnet DC User Manual

Includes mounting and installation
Hide thumbs Also See for FLEXnet DC:
Table of Contents

Advertisement

FLEXNet DC Measurements

The FLEXNet DC can measure and record:
• Volts for one battery bank*
• Amps**
• KiloWatts
• kWhrs removed from the batteries
• kWhrs returned to the batteries
• Amp hours removed from the batteries
• Amp hours returned to the batteries
• Battery bank state-of-charge
• Lifetime kiloamp hours removed from the batteries***
• Days since charge parameters last met
• Lowest battery state-of-charge reached
• Minimum battery voltage***
• Maximum battery voltage***
• Maximum amp charged***
• Maximum amp discharged***
• Maximum kWhrs charged***
• Maximum kWhrs discharged***
*
Battery volt input: 0-80 VDC in .1 volt resolution
**
2000 amp DC span (+/- 1000 amps DC—net amps are charging, net amps
are discharging), .1 amp resolution
***
The user can manually reset these data. At any given time, the values
displayed are the most recent since the values were last displayed
11

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FLEXnet DC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents