To Connect The User Interface - Daikin EHBH04CA Installation Manual

Altherma low temperature split
Hide thumbs Also See for EHBH04CA:
Table of Contents

Advertisement

Backup heater
Connections to
type
(a)
backup heater power
supply
3 kW 1~ 230 V
F1B
(*3V)
L N
L N
3 kW 1~ 230 V
F1B
(*9W)
L
L
N
N
6 kW 1~ 230 V
(*9W)
6 kW 3~ 230 V
F1B
(*9W)
L1 L2 L3
L1 L2 L3
6 kW 3N~ 400 V
F1B
(*9W)
9 kW 3N~ 400 V
L1 L2 L3
L1 L2 L3
(*9W)
(a) For configuration of the backup heater, see "4.2.2 Quick wizard:
Standard" on page 13.
2 Fix the cable with cable ties to the cable tie mountings.
3 Configure the user interface for the respective power supply.
See "4.2.2 Quick wizard: Standard" on page 13.
During connection of the backup heater, miswiring is possible. To
detect possible miswiring, it is highly recommended to measure the
resistance value of the heater elements. Depending on the different
backup heater types, following resistance values (see table below)
should be measured. ALWAYS measure the resistance on the
contactor clamps K1M, K2M, and K5M.
3 kW
6 kW
1~
1~
230 V
230 V
K1M/1
K5M/13 52.9Ω
52.9Ω
K1M/3
K1M/5
K1M/3
K1M/5
26.5Ω
26.5Ω
K2M/1
K5M/13 ∞
26.5Ω
K2M/3
K2M/5
K2M/3
K2M/5
52.9Ω
52.9Ω
EHBH/X04~16CA
Daikin Altherma - Low Temperature Split
4P313771-1C – 2012.11
Connections to
terminals
X6M
X7M
1 2 3 4
5
6 7 8
X6M
X7M
1 2 3 4
5
6 7 8
X6M
X7M
1 2 3 4
5
6 7 8
X6M
X7M
1 2 3 4
5
6 7 8
6 kW
6 kW
9 kW
3~
3N~
3N~
230 V
400 V
400 V
52.9Ω
105.8Ω
105.8Ω
105.8Ω
105.8Ω
26.5Ω
105.8Ω
105.8Ω
26.5Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
3 kW
6 kW
1~
1~
230 V
230 V
K1M/5
K2M/1
Example measure resistance between K1M/1 and K5M/13:
K1M
1 3 5 13
2 4 6 14
Ω
Ω
K5M
1 3 5 13
2 4 6 14
3.5.5

To connect the user interface

1 Connect the user interface cable to the indoor unit.
2 1
X5M
X2M
A2P
A2P
a
b
a User interface delivered with the unit
b Optional user interface
2 Fix the cable with cable ties to the cable tie mountings.
Fixation of the user interface to the indoor unit
3 Insert a screwdriver into the slots underneath the user interface
and carefully separate the faceplate from the wallplate.
NOTICE
The PCB is mounted in the faceplate of the user interface.
Be careful NOT to damage it.
4 Fix the wallplate of the user interface to the frontplate of the
unit.
3 Installation
6 kW
6 kW
9 kW
3~
3N~
3N~
230 V
400 V
400 V
K2M
K2M
1 3 5 13
2 4 6 14
Installation manual