4 Calibrate Mode
4-1

Display Method of Calibrate Mode

There are 2 methods for entering into Calibrate Mode.
(1) Set the DIP switches SW1 and SW2 on the back side respectively to OFF and ON.
Press the Reset switch, restart the NB Unit, and then it enters into the Calibrate Mode.
(2) Place a "Function Key" component in the window, and set its function to "Touch Calibration".
Click this icon to start Calibrate Mode.
4-2

Functions of Calibrate Mode

Procedures to carry out Calibrate Mode:
Track and touch the "+" displayed on the screen and you will hear a "click". Carry on with this, until the
"+" disappear followed by a "TP Adjust Success!" turning up on the screen. Set both of the DIP switches
SW1 and SW2 to OFF, press the Reset switch again.
4-3
On-line Touch-control Calibration
Function
Besides using the DIP switches, Touch-control Calibration can also be achieved with a function key
while the software is running, thus sparing the time of equipment adjustment and the trouble of opening
the control panel. For details, refer to 3-7-2 Function Key in the NB-Designer Operation Manual.
4-2
NB-series Programmable Terminals Setup Manual(V107)