INSTALLATION INSTRUCTIONS
Both ends open
Construction of Enclosure
Enclosure must be stable and be constructed of non combustible materials.
Enclosure and fire must be installed above ground level and have adequate drainage.
The enclosure must have a minimum of 2 vents with each vent having a total open area of
11000mm
73mm x 150mm) or larger. Ventilation allows for residual heat and unburnt gases to escape
the enclosure.
An access panel / door must be fitted to allow access/ servicing of the gas valve and controller.
Recommended access door size 300 x 400mm or larger.
Where valve assembly cannot be reached a manhole access panel may be required.
All appliances must have an isolation gas valve fitted, accessible and external to the appliance
enclosure.
Lighting Instructions
8
Example 3
30% or more in total
of the remaining wall
area is open and
unrestricted
Open side at least
25% of total wall area
. Vents are to be located at the upper and lower sections of the enclosure. (EG
2
Rotate gas knob to pilot position.
Push knob in and hold to spark.
Once pilot is alight, hold knob in for a further 10 seconds.
Release knob and rotate to the on position.
To turn the appliance off, rotate the knob to the off position.
(continued)
Open side at least
25% of total wall area
Example 5
30% or more in total
of the remaining wall
area is open and
unrestricted
Example 4