INSTALLATION INSTRUCTIONS
Construction of Enclosure (continued)
TYPICAL MASONRY / BRICKWORK SURROUND
750mm min
enclosure
height
TYPICAL FIXED TABLE / FABRICATED ENCLOSURE
750mm min
height
NOTE - The enclosure must have 2 vents of at least 11000mm2 per vent. (EG 73mm x 150mm) or
larger.
Warranty requirement – The enclosure must be constructed on a stable surface.
The weight of the appliance must be supported by the pan, not by the control box.
The appliance must be installed level.
The interior of the enclosure must not be filled with any media. Keep all area around tray and
valve enclosure free and well ventilated.
LPG gas cylinders must not be stored in the enclosure.
LPG storage enclosures must meet the requirements of AS/NZS5601.1-2013.
It is recommended that reconstituted stone be kept away from the heat and flame, due to the risk
of cracking. The manufacturer is not responsible for damage.
Note – Radiant heat from the appliance may effect certain materials or items stored near or
14
under the appliance and may be seriously damaged.
150mm
Enclosure
height
(continued)
Access door 300 x 400mm min
Access door 300 x 400mm min
Enclosure constructed
from non-combustible
materials
Ventilation
Ventilation
Glass or similar fixed barrier
20mm air gap under glass or similar
fixed barrier
Table or similar enclosure
constructed from non-combustible
materials
Ventilation
Ventilation