Wiring Procedure; Power Supply; Earthing The Oplc - Unitronics V1210-T20BJ Installation Manual

Table of Contents

Advertisement

Installation Guide
Wiring
 Do not touch live wires.
 Install an external circuit breaker. Guard against short-circuiting in external wiring.
 Use appropriate circuit protection devices.
 Unused pins should not be connected. Ignoring this directive may damage the device.
 Double-check all wiring before turning on the power supply.
 To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
 Do not use tin, solder, or any substance on stripped wire that might cause the wire
Caution
strand to break.
 Install at maximum distance from high-voltage cables and power equipment.

Wiring Procedure

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.

Power Supply

The controller V1210-T20BJ requires either an external 12 or 24VDC power supply.
Permissible input voltage range: 10.2-28.8VDC, with less than 10% ripple.
 The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class 2/Limited Power.
 Do not connect either the 'Neutral or 'Line' signal of the 110/220VAC to device's 0V pin.
 Install an external circuit breaker. Guard against short-
circuiting in external wiring.
 Double-check all wiring before turning on the power
supply.
 In the event of voltage fluctuations or non-conformity to
voltage power supply specifications, connect the device
to a regulated power supply.

Earthing the OPLC

To maximize system performance, avoid electromagnetic interference by:
 Mounting the controller on a metal panel.
 Connect the functional earth terminal of the OPLC, and the common and ground lines of
I/Os, directly to the earth ground of your system.
 For ground wiring, use the shortest and thickest possible wire.
Unitronics
Vision™ OPLC™,V1210-T20BJ
2