ESIE11-05
8.2.11 [A] Option Setup
Caution
Glycol concentrations lower than the set parameter will cause freezing of the liquid.
8.2.12 [b] Settings Are Not Applicable
Not applicable.
8.2.13 [C] Leaving Water Temperature Limits
To prevent misuse concerning leaving water temperatures, it is possible to limit the set points.
8.2.14 [d] Settings Are Not Applicable
Not applicable.
Functional Description
[A-00] Setting is not applicable.
[A-01] Setting is not applicable.
[A-02] Setting is not applicable.
[A-03] Leaving water temperature overshoot/undershoot value
This setting makes it possible to set the allowable overshoot (heating)/undershoot (cooling)
when operating the unit during leaving water control. See "Thermostat Control" on page 63.
[A-04] Glycol concentration setting
This setting is only applicable for units with a low temperature cooling option.
When changing this setting, the freeze prevention parameters will be changed in relation
with the glycol concentration.
[A-04]=0, minimum leaving water = 0°C.
[A-04]=1, minimum leaving water = -10°C.
[C-00] Maximum leaving water setpoint in heating operation.
[C-01] Minimum leaving water setpoint in heating operation.
[C-02] Maximum leaving water setpoint in cooling operation.
[C-03] Minimum leaving water setpoint in cooling operation.
Depends on field setting [A-04]
when [A-04]=0, the minimum value is set to 5
when [A-04]=1, the minimum value is set to 0 (*1)
(*1) only for EW*Q*BAW*B* units
[C-04] Field setting not applicable.