Advertisement

Options
5.2.4 Field Setting
How to set
1. Unit field setting
demand control
in the field
2. External control adaptor settings
The contents of the various settings for unified switching of demand and low noise operation are
as follows:
196
 Setting mode 1
Turn on low noise control like explained in the manual of the unit.
 Setting mode 2
Match low noise and demand addresses to the external control address.
Match address setting DIP switches DS1 and DS2 to the low noise and demand addresses
of the unit.
Divide the outdoor modules for demand control and low noise control into units to be switched
together (hereinafter refered to as "demand control group").
An adaptor is required for each demand control group.
Set the 5-bit demand address of the adaptor and outdoor modules.
Set the service mode for the outdoor modules by operating the switches on the PCB outdoor
module assembly (see "To set the outdoor modules demand address to number 7").
The adaptor is set by DS1 and DS2 (see "To set the 5-bit cool/heat address by DS1 and DS2").
Field setting start
Field setting complete
ESIE11-05
Service Procedure