Indoor/outdoor unit installation diagram
50 cm
or more
Protection
vinyl
6 m or
Maximum
less
allowable piping
elevation 10 m
or less
38
S-east_MEMORY_IBIM_EN_03955A-02_EN.indd 38
Installation space for floor type indoor unit
f To minimize the waste of space due to installation, install the indoor unit as
f
shown in below figure.
- Top view
❋ ❋ After completing the installation, remove the protection vinyl.
(Be careful of static electricity).
❋ ❋ After completing the installation, remove the protective
filament film on the product.
• Make sure that there are no obstacles (such as curtains etc.) blocking air
inlets of the indoor unit.
CAUTION
• Clear space on the right side of the indoor unit for possible filter
maintenance in the future.
Piping length for indoor/outdoor unit installation
f Refer to illustration on the left for maximum allowable
f
piping length and elevation.
f Since product performance and lifespan may decrease as
f
piping length becomes longer, try to minimize the piping
length but make sure it is over 5 m.
f Select the installation location where you can keep the
f
piping bending to maximum 10 spots.
f Stated cooling performance is based on product with 5 m
f
piping.
Install S-trap for
every 6 m
CAUTION
Maximum allowable
piping length 20 m
or less
30 cm or more
Outdoor unit
Air guide
(Not provided by
manufacturer )
Outdoor
unit leg
Rubber leg
20 cm or more
Spare space for piping
When air guide needs to be installed to prevent the warm discharge air from
disturbing the pedestrian, refer to the illustration on the right side for installation.
• One S-trap must be installed on the low pressure
pipe up to 6 m of piping elevation. For piping
elevation that exceeds 6m, install S-trap every
6 m.