Advertisement

Air Conditioner
Air Conditioner
user & installation manual
user & installation manual
imagine
imagine
Thank you for purchasing this Samsung product.
Thank you for purchasing this Samsung product.
the possibilities
the possibilities
AF✴✴HV Series
AF✴✴HV Series

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AF HV Series

  • Page 1 AF✴✴HV Series AF✴✴HV Series Air Conditioner Air Conditioner user & installation manual user & installation manual imagine imagine the possibilities the possibilities Thank you for purchasing this Samsung product. Thank you for purchasing this Samsung product.
  • Page 2: Table Of Contents

    Contents Preaparation Safety precautions ..................... . . 3 Checking before use .
  • Page 3: Safety Precautions

    If you have any questions, call your nearest contact center or find help and information online at www. samsung.com. These warning signs are here to prevent injury to you and others. Please follow them carefully.
  • Page 4 Safety precautions FOR INSTALLATION WARNING Use the power line with the power specifications of the product or higher and use the power line for this appliance only. In addition, do not use an extension line. Extending the power line may result in electric shock or fire. Do not use an electric transformer.
  • Page 5 FOR INSTALLATION CAUTION Install your appliance on a level and hard floor that can support its weight. Failing to do so may result in abnormal vibrations, noise, or problems with the product. Install the draining hose properly so that water is drained correctly. Failing to do so may result in water overflowing and property damage.
  • Page 6 Safety precautions FOR USING WARNING If the appliance is flooded, please contact your nearest service center. Failing to do so may result in electric shock or fire. If the appliance generates a strange noise, a burning smell or smoke, unplug the power plug immediately and contact your nearest service center.
  • Page 7 FOR USING WARNING Do not insert your fingers or foreign substances into the outlet when the air conditioner is operating or the air flow blade is closing. Take special care that children do not injure themselves by inserting their fingers into the product.
  • Page 8 Safety precautions FOR USING CAUTION Do not place objects or devices under the indoor unit. Water dripping from the indoor unit may result in fire or property damage. Check that the installation frame of the outdoor unit is not broken at least once a year.
  • Page 9 FOR CLEANING WARNING Do not clean the appliance by spraying water directly onto it. Do not use benzene, thinner, alcohol or acetone to clean the appliance. This may result in discoloration, deformation, damage, electric shock or fire. Before cleaning or performing maintenance, unplug the air conditioner from the wall socket and wait until the fan stops.
  • Page 10: Checking Before Use

    Checking before use Using indoor unit Make sure that curtain does not block the air inlet. It may decrease cooling performance by blocking air circulation. In Cool mode, set the appropriate desired temperature. If the desired temperature is too low, it may be harmful for human body and power consumption will also increase. Set the desired temperature about 5 °C lower than the outdoor temperature.
  • Page 11 Checking auxiliary power switch Turn on the auxiliary power switch which is installed separately. 1 phase circuit breaker 3 phase 4 wire circuit breaker Auxiliary power switch(ELCB, ELB) • Auxiliary power switch is not included in the package. Purchase and install it separately. NOTE •...
  • Page 12: Checking The Name Of The Parts

    Checking the name of the parts The picture and function of the indoor unit may be different depending on the model. Main parts AF30HV Series Air flow blade (right/left orientation) Air flow blade (up/down orientation) Air outlet Virus doctor Control panel Air filter Removes the dust of incoming air Air intake...
  • Page 13 AF50HV Series Air flow blade (up/down orientation) Opens and closes automatically according to power on/off Air flow blade (right/left orientation) Air outlet Virus doctor Control panel Air filter Removes the dust of incoming air Remote controller slot Air intake Intakes the outdoor air To open the panel Hold the upper part of the panel, and then pull it slightly forward.
  • Page 14 Checking the name of the parts Control panel and the display You can operate the air conditioner with the control panel when you can’t or don’t want to operate the air conditioner with the remote controller. (see page 27) Fan speed indicator Air swing (Up/Down) indicator Temperature setting Air swing (Left/Right) indicator...
  • Page 15: Checking The Remote Controller

    Checking the remote controller Remote controller buttons You can activate the air conditioner by pointing the remote controller away from it. When using the remote controller, always point it directly at the air conditioner. Vertical air swing Adjusts the air flow direction up and down (Not applicable to Duct type models).
  • Page 16 Checking the remote controller Remote controller display Remote controller Set temperature or on/off set transmission time with the timer function Low battery On/Off timer Fan speed Operation mode *Heat mode is not supported Air flow direction by this model. Options * These functions are not supported •...
  • Page 17 Battery changing time When the battery is exhausted,( )will be displayed in the remote controller display. When the icon appears, change the batteries. The remote controller requires two 1.5V AAA type batteries. Storing the remote controller When you do not use the remote controller for a long time, remove the batteries from the remote controller and store it in the remote controller holder.
  • Page 18: Basic Operation

    Basic operation Basic operation is an operation mode that can be selected by pressing the Mode button. Auto In Auto mode, the air conditioner will automatically set the Operation(Cool/Heat Mode) and fan speed depending on the room temperature detected by the room temperature sensor. •...
  • Page 19 Turning on the power Press the button to turn on the air conditioner. Selecting the operation mode (Heat mode is not supported by this model) Press the button to set the operation mode. Selecting the fan speed (Heat mode is not supported by this model) Press the button to set the desired fan speed.
  • Page 20 Basic operation Selecting air flow direction This function allows you to shift the air flow direction up and down or left and right. Press the button to move the air flow direction up and down or left and right while the air conditioner is turned on.
  • Page 21: Setting The On/Off Timer

    Setting the On/Off timer You can set the air conditioner to turn on/off automatically at desired time. Setting On timer while the air conditioner is off / Off timer while the air conditioner is on. When the air conditioner is off; 1.
  • Page 22 Setting the On/Off timer When the air conditioner is on; 1. Press the Timer button to select (Off). - (Off) indicator starts to blink and you can set the time. 2. Press the < or > button to set the time. - You can set the time in 0.5 hour unit from 0.5 ~ 3 hours and 1 hour unit from 3~24 hours.
  • Page 23: Using The Turbo Function

    Using the Turbo function You can set the Turbo function to provide fast and powerful cooling (heating). When the air conditioner is operating in Cool or Heat mode; 1. Press the Turbo button. - (Turbo) will be displayed and the function will operate for 30 minutes. Cancel Press the Turbo Button.
  • Page 24: Locking The Control Panel

    Locking the control panel You can lock the control panel on the indoor unit to prevent the children from playing with the air conditioner.  and Press the Temp buttons for 3 seconds. You will hear ring and the Lock ( ) icon will appear on the indoor unit display. Once Lock is set, you cannot control the air conditioner with the control panel but you can only control it with the remote controller.
  • Page 25: Using The Air Conditioner With The Control Panel

    Using the air conditioner with the control panel You can control the air conditioner without the remote controller. 1. Press the Power button on the indoor unit control panel. The air conditioner will turn on with ringing sound. Stop To turn off the air conditioner, press the Power button again.
  • Page 26: Cleaning And Maintaining The Air Conditioner

    Cleaning and maintaining the air conditioner • Make sure the power is turned off and unplugged from the wall socket when cleaning the air conditioner. CAUTION Cleaning the indoor unit Wipe the surface of the unit with a slightly wet or dry cloth when needed. Brush away the dust on the narrow gap of air conditioner.
  • Page 27 Cleaning the Air filter Washable air filter captures large particles from the air. The filter can be cleaned with a vacuum or by hand washing. 1. Remove the tape that holds the air filter and open the panel and pull out the air filter out. Pull out the air filter in the direction of the arrow as shown in the figure.
  • Page 28 Cleaning and maintaining the air conditioner Maintaining your air conditioner If the air conditioner will not be used for an extended period of time, dry the air conditioner to maintain it in best condition. 1. Dry the air conditioner thoroughly by operating in Fan mode for 3 to 4 hours and turn off the circuit breaker. There may be internal damage if moisture is left in components.
  • Page 29: Troubleshooting

    Troubleshooting PROBLEM SOLUTION • Check power status and then operate the air conditioner again. • Check whether the power plug is connected correctly or the auxiliary power switch The air conditioner does not is switched on. work at all. • If the air conditioner is switched off by the Timer function, press the Power button.
  • Page 30 Troubleshooting PROBLEM SOLUTION • Check if you have finalized the setting by pressing the Set button. If you haven't, you Timer function is not working. need to set the timer again and press the Set button. • Odor may permeate depending on the surrounding environment or operating condition.
  • Page 31 Operation ranges The table below indicates the temperature and humidity ranges the air conditioner can be operated within. Refer to the table for efficient use. OPERATIONAL TEMPERATURE INDOOR MODE IF OUT OF CONDITIONS HUMIDITY INDOOR OUTDOOR Condensation may occur on the indoor Cool unit with risk to have either water blow 18 ˚C to 32 ˚C...
  • Page 32: Safety Precautions

    In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
  • Page 33 Installing the unit IMPORTANT : When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always disassemble the electric lines before the refrigerant tubes. Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer).
  • Page 34 Safety precautions Power supply line, fuse or circuit breaker Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance with current local safety standards. Always verify that a suitable grounding connection is available. Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to ensure the operation of any other domestic appliance connected to the same electric lines.
  • Page 35: Installing The Air Conditioner

    Installing the air conditioner Required tools General tools (1) Vacuum pump (2) Torque wrench (3) Pipe cutter (4) Reamer (5) Pipe bender (6) Spirit level (7) Screw driver (8) Spanner (9) Drill (10) L wrench (11) Measuring tape Tools for trial operation (1) Thermometer (2) Resistance meter (3) Electroscope...
  • Page 36 Installing the air conditioner When installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze. If you can not find a adequate place without direct see breeze, protection wall should be constructed. Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which can damage the outdoor unit.
  • Page 37 If enough ventilation space is not secured, the product may malfunction. Keep in mind that SAMSUNG logo is located on the front side of outdoor unit. Single installation (Unit : mm) ❇...
  • Page 38 Installing the air conditioner When installing more than 1 outdoor unit (Unit : mm) ❇ When the air outlet is towards the wall 300 or more 600 or more 600 or more 600 or more ❇ When 3 sides of the outdoor unit are blocked by the wall 300 or more 300 or more 600 or more...
  • Page 39 Outdoor unit installation 1. To prevent vibration and noise, fix the outdoor unit firmly and check that base ground is hard enough and has no slopped surface. (Fix the outdoor unit with M10 bolts, nuts and washer.) 2. Appropriate length of the bolt must be over 20 mm from the surface of the ground. 3.
  • Page 40 Installing the air conditioner Refrigerant pipe work Insulating the pipes Make sure to insulated the refrigerant pipes with an insulation tape. If the Pipe insulator pipe is not insulated, condensate may form and drop into the indoor. Vinyl Wind the refrigerant pipes and the drain hose with vinyl tapes. tape Indoor/ When you bend the pipe, try to secure large bending radius (over 100 mm)
  • Page 41 Refrigerant piping work 1. Cut the pipe with a pipe cutter ensuring that the cut edge remains flat and then remove all the burrs. 2. Make sure that the flared pipe doesn’t have uneven thickness, damaged and cracked surfaces, or any other defects. 3.
  • Page 42 Installing the air conditioner Electrical work Wiring work must be done by the certified expert. Wiring work should be performed in accordance with related laws such as technical specification on electric installation or installation guide. You must install exclusive power supply. - If you use multi-outlet, there is a risk of electric shock or fire.
  • Page 43 • Please use rated wires or products (with heat resistance over 105 °C) of all the wires and the switches or fuses in the cabinet panel. (Retailer and installer is responsible for the use of parts that does not meet the wire standards CAUTION or capacity requirements) •...
  • Page 44 Installing the air conditioner Connecting the power terminal Connect the cables to the terminal board with solderless ring terminals. Only sue the certified and rated cables and make sure to firmly connect them without applying any external force to the terminal.
  • Page 45 Connecting the wires AF30HV Series Product uses single phase, 220 -240 V power supply. When connecting indoor and outdoor unit connection cable, make sure to match the numbers (or letters) on outdoor unit side to indoor unit side. Make sure to connect the indoor and outdoor unit communication cable to the connector within the electrical component box of each unit.
  • Page 46 Installing the air conditioner Order of electrical connection AF30HV Series Entire system diagram Power cable Communication cable Electrical panel Outdoor Communication cable unit NFB Single phase 220 - 240 V, 50 Hz Ground wire Ground wire Indoor/Outdoor Indoor unit unit connection cable Power wiring diagram Cable clamp Communication cable...
  • Page 47 AF50HV Series Entire system diagram Power supply cable Communication cable Electrical panel Outdoor unit Communication cable NFB 3 phase 4 wires 380 - 415 V, 50 Hz Ground wire Ground wire Indoor/Outdoor unit connection cable Indoor unit Power wiring diagram Cable clamp Indoor/outdoor Communication power supply cable cable Power supply cable...
  • Page 48 Installing the air conditioner How to connect your extended power cables 1. Prepare the following tools. Connection sleeve Contraction tube Tools Crimping pliers Insulation tape (mm) (mm) Spec MH-14 20xØ6.5(HxOD) Width 19 mm 70xØ8.0 (LxOD) Shape 2. As shown in the figure, peel off the shields from the rubber and wire of the Power cable power cable.
  • Page 49 4. Using a crimping tool, compress the two points and flip it over and compress another two points in the same location. - The compression dimension should be 8.0. - After compressing it, pull both sides of the wire to make sure it is firmly pressed. Method 1 Method 2 Compression...
  • Page 50 Installing the air conditioner Installing the interface module AF30HV Series 1. Remove the cover of the electrical component box. Separate the cabinet on top part of the outdoor unit. 2. Attach the interface module Refer to the illustration for the location and attach the interface module. When you attach the interface module, make sure that it doesn’t get tangled with the wires or other parts.
  • Page 51 AF50HV Series 1. Remove the cover of the electrical component box. Separate the cabinet on the side of the outdoor unit. 2. Attach the interface module Refer to the illustration for the location and attach the interface module. When you attach the interface module, make sure that it doesn’t get tangled with the wires or other parts.
  • Page 52 Installing the air conditioner Vacuuming, gas leak test and charging additional refrigerant Air tightness test and vacuuming Use Nitrogen gas for air tightness test as shown in the illustration. Manifold gage Low pressure side High pressure side Vacuum pump 1. Execute air tightness test with nitrogen gas at pressure over 0.2 MPa and below 4.1 MPa. If you apply pressure at over 4.1 MPa, pipes may get damaged.
  • Page 53 Charging the refrigerant and preventing refrigerant leakage 1. Measure the quantity of the refrigerant according to the length of Manifold gage the liquid side pipe. Then, Add fixed quantity of the refrigerant using Outdoor unit High a scale. (When the pipe length exceeds the standard pipe length of pressure Gas side 5 m, charge the additional amount of refrigerant according to the...
  • Page 54 Installing the air conditioner Fixing and insulating the connection part of the pipe Check the leakage on the connection part of pipes and make sure the insulated them afterwards. Pipe must be insulated properly so that condensation does not form. Use foamed polyethylene with thickness over 5 mm to insulate the High pressure pipe...
  • Page 55 Connecting drain hose of indoor and outdoor unit 1. To prevent condensation from forming on the drain hose, insulated Drain hose the drain hose with a supplied insulator. Insulation 2. Connect the drain hose by pushing the extension drain hose to the insulated drain Drain hose pipe.
  • Page 56 Installing the air conditioner 4. After connecting the drain hose, use a water bottle to pour water into the air outlet of the indoor unit to check the drainage. (To prevent water from flowing all over the place, insert the water bottle deeply into the first blade on the left side of the air outlet and slowly pour water.
  • Page 57 Trial operation and switch operation specification Outdoor unit type A: Located in Sub PCB Outdoor unit type B: Located in Main PCB Key Switch 7-segment display 7-segment display Key Switch [Single phase: AF30HV Series] [3 phase: AF50HV Series] 1. Check the power between the outdoor unit and the cabinet panel. Single phase power supply: L, N 3 phase power supply: R, S, T, N R-S, S-T, R-T : 380 V is normal.
  • Page 58 Installing the air conditioner Display Control type Item SEG1 SEG2 SEG3 SEG4 1 time Heating trial operation Defrost trial operation Short press times End KEY operation times 1 time Cooling trial operation Short press End KEY operation times Short press 1 time RESET 1 time...
  • Page 59 Display Control type Item SEG1 SEG2 SEG3 SEG4 Protection control Frequency status 0: No protection control 0: Normal 0: Cooling 1: Frozen 1: Hold Protection control times 1: Heating 2: Non-stop defrost 2: Down 3: Overload 3: Up_limit Short press 4: Discharge 4: Down_limit 5: Full current...
  • Page 60 Installing the air conditioner Eco mode: Displays energy saving mode or standby mode Eco mode display Key Switch 7-segment display 7-segment display Key Switch [AF30HV Series] [AF50HV Series] ❇ No separate Eco mode display ❇ Eco mode is displayed in lamp Model series AF30HV Series Display...
  • Page 61 Failure diagnosis When error occurs during operation, error mode will appear on the outdoor unit MAIN PCB display and inverter PCB display. Error Measures to be taken by service Description Measures to be taken by installer code technician 1. Re-connect the connector Indoor room E121 1.
  • Page 62 Installing the air conditioner Error Measures to be taken by service Description Measures to be taken by installer code technician 1. Check opening of the service valve 1. Open service valve Blockage on high 2. Check the connection status of 2.
  • Page 63 Error Measures to be taken by service Description Measures to be taken by installer code technician E484 PFC overload error 1. Replace the PBA Input current sensor E485 1. Replace the outdoor unit PBA error 1. Check the location of the outdoor unit when temperature of a heat insulating 1.
  • Page 64 QUESTIONS OR COMMENTS? COUNTRY CALL OR VISIT US ONLINE AT Ghana 0800-100-077 www.samsung.com/africa_en/support...