shutdown. Then move the switch to the AUTO or RUN
position.
Generator sets with serial numbers below 2051415
were built with controllers equipped with the continuous
power mode jumper. If the power jumper is removed
Code Fault
HB
High battery
voltage warning
LB
Low battery
voltage warning
Figure 4-5 Fault Warning Codes
38
Section 4 ADC 2100 and DC 2200 Controllers
Downloaded from
www.Manualslib.com
Description
Fault code is displayed if the engine starting battery voltage
rises above 16 VDC for a 12 VDC system or above 30 VDC
for a 24 VDC system for more than one minute when the
engine is not running. This fault condition does not inhibit
engine starting.
The fault condition clears when the battery voltage returns to
a voltage within the limits for more than 10 seconds.
Fault code is displayed if the engine starting battery voltage
falls below 8 VDC for a 12 VDC system or below 16 VDC for
a 24 VDC system for more than one minute when the engine
is not running. This fault condition does not inhibit engine
starting.
The fault condition clears when the battery voltage returns to
a voltage within the limits for more than 10 seconds.
manuals search engine
and the controller powers down after a fault shutdown,
move the master switch to OFF/RESET and then to
RUN to display the fault code. Then move the switch to
OFF/RESET again to clear the fault. See Section 4.6 for
more information on the continuous power mode
jumper.
Check
Check the battery rating and
condition.
Check the battery charger
operation.
Check the battery rating and
condition.
Check the battery charger
operation.
Charge or replace the battery.