5.2.3
Keypad
The three-button keypad is a feature of the ADC-RES
controller. The keypad is used to check system status,
change controller settings, and adjust the generator set
output voltage and frequency.
When the generator set is running, press the up and
down arrow buttons to step through system status
displays as shown in Figure 5-5. After 10 seconds, the
display returns to engine runtime hours.
Use the configuration and adjustment menus to change
controller settings and adjust the generator set output. A
password key sequence is required to enter the
configuration and adjustment menus.
contains the instructions to enter the configuration and
adjustment menus and change the settings using the
controller keypad.
The DC-RET controller is not equipped with a keypad.
DC-RET controllers are factory-set and not adjustable.
TP-6196 10/09
Downloaded from
www.Manualslib.com
Item
Description
Runtime hours
Displays total generator set runtime hours while the generator set is running
and when no other codes are displayed.
Metering display
Displays AC voltage (output), frequency, and battery voltage. Press the up or
(ADC-RES only)
down arrow when runtime hours are displayed to step through these displays.
Crank indication
Displays CC_1, CC_2, or CC_3 to indicate the first, second, or third attempt to
start the engine. The last digit flashes during the crank cycle rest periods.
Software version
ADC-RES: The software version number (v#.##) is displayed when entering
number
configuration mode. See the installation manual.
DC-RET: The software version number (v#.##) is displayed during the first
2 seconds of the crank cycle.
Fault codes
Flashes a 2- or 3-letter fault code to indicate various fault conditions.
See Section 4.4.
Select and arrow
Use the arrow buttons to step through the data displays. See Section 5.2.3.
buttons
The keypad is also used for controller setup and adjustment. The setup and
adjustment functions are password-protected. Have setup and adjustments
performed only by an authorized distributor/dealer.
Three-position
Switch functions as the generator set operation and controller reset switch.
switch
Section 4.5
manuals search engine
Engine Runtime
XXX.X hours
Output Voltage
VAC
Output Frequency
Hz
Battery Voltage
VDC
Notes:
Generator set master switch in AUTO.
Step through using up or down arrow buttons.
After 10 seconds, display returns to runtime hours.
Figure 5-5 Generator Set Status Displays
(ADC-RES only)
Section 5 ADC-RES and DC-RET Controller
tp6515
55