Auto Restart Control; Indoor Fan Motor Control - Panasonic CS-VA70KE Service Manual

Hide thumbs Also See for CS-VA70KE:
Table of Contents

Advertisement

CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE
8.6.

AUTO RESTART CONTROL

· If there is a power failure, operation will be restarted automatically when the power is resumed.
It will start with the previous operation mode and airflow direction.
(Time Delay Safety Control is valid)
· Auto Restart Control is not available when Timer or Sleep Mode is set.
· This control can be omitted by cutting the jumper wire J2.(Refer Circuit Diagram)
8.7.

INDOOR FAN MOTOR CONTROL

· Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
· Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button.
Fan Speed
No.
Manual
Cooling
Auto
Sleep
Soft Dry
Manual
Heating
Auto
Sleep
Voltage to Fan
CS-VA70KE
Motor Drive
CS-VA90KE
Transistor (V)
CS-VA120KE
8
7
6
21.0
21.0
18.6
26.7
25.9
21.5
32.0
31.0
26.0
SHi
Hi
Me
High Speed ←→ Low Speed
5
4
3
17.0
15.8
11.0
18.1
15.8
11.0
22.5
21.5
16.5
Lo
Lo-
SLo
28
2
1
0
11.0
7.2
0
11.0
7.2
0
11.0
7.2
0
MID
START
STOP
START