Humidity Control Settings

Confi gures humidity control settings (dehumidi-
fi cation/humidifi cation).
Humidity Mode
Determines active humidity mode(s). Valid
selections: Humidifi cation (This logic will
communicate a Humidifi cation output when
the space humidity is less than the setpoint i.e.
acts as a humidistat. When the Humidifi cation
output is active, the fan output will also be
active. The Humidifi cation output will not be
communicated when the space humidity is
above the setpoint.), Dehumidifi cation (This
logic will reduce the cooling airfl ow when the
space humidity is greater than the setpoint
to improve dehumidifi cation i.e. acts as a
dehumidistat. The cooling airfl ow will not be
reduced when the space humidity is below the
setpoint.), Both, or None.

Service Mode

Unit – EXM Controller
Model Displays the unit model number
Serial Number Displays the unit serial
number
Manual Operation Manual Operation mode
allows the service technician to manually
command operation for any of the thermostat
outputs, blower speed, as well as pump
To confi gure the
humidity control
settings on the iGate
Connect thermostat:
From the Home screen,
press MENU.
Select
Settings
Installation.
Select
Humidity
To confi gure the service
mode on the iGate
Connect thermostat:
From the Home screen,
press MENU.
Select
Settings
Installation.
Select
Service
Mode.
Control.