ClimateMaster iGate Connect Installation Manual page 20

Table of Contents

Advertisement

16
from the ductwork during maximum capacity
operation. Range will depend on model and
maximum cooling capacity selection.
Low Dehum Airfl ow Confi gures the unit
airfl ow while operating at minimum capacity
in the dehumidifi cation mode. Range will
depend on model and minimum cooling
capacity selection.
High Dehum Airfl ow Confi gures the unit
airfl ow while operating at maximum capacity
in the dehumidifi cation mode. Range will
depend on model and maximum cooling
capacity selection.
Constant Fan Airfl ow Confi gures the unit
airfl ow while operating in the continuous fan
mode. Range will depend on unit model.
Heat Off Delay This setting determines
whether or not (and how long) the blower will
continue to operate after the compressor has
cycled off at the end of each heating cycle.
Valid range: 0 seconds to 255 seconds.
Cool Off Delay This setting determines
whether or not (and how long) the blower will
continue to operate after the compressor has
cycled off at the end of each cooling cycle.
Valid range: 0 seconds to 255 seconds.
Unit Confi guration
The Unit Confi guration settings allow the
installing technician to confi gure the thermostat
to the installed equipment. NOTE. Unit
Confi g is only necessary when replacing an
EXM controller. The Unit Confi g settings are
programmed at the factory when the unit is
built.
Heat Pump Family Select the family of heat
pump installed.