Installation Instruction; Select The Best Location; Indoor/Outdoor Unit Installation Diagram - Panasonic CS-PW18GKE Service Manual

Table of Contents

Advertisement

11 Installation Instruction

11.1. Select The Best Location

INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over 7.5 m, additional refrigerant should be
added as shown in the table.
Piping size
Rated
Length
Elevation
(m)
Gas
Liquid
1/2"
1/4"
5
If the unit is installed at 10 m distance, the quantity of additional
refrigerant should be 50g ...... 20 g/m = 50 g
Max
Min.
Max.
Piping
Piping
Refrigerant
(m)
Length
Length
(m)
(m)
20
3
25
11.2. Indoor/Outdoor Unit
Additional
(g/m)
20
19
Installation Diagram