Fujitsu AW*Z24LBC Service Instruction page 59

Ceiling wall inverter
Hide thumbs Also See for AW*Z24LBC:
Table of Contents

Advertisement

Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AW * Z24LBC
[Condition]
Ambient
Indoor 15 - 23degC, Outdoor 2 - 12degC
temperature
Refrigerant
Standard amount
amount
Piping
7.5m (Height difference 1m)
length
Power
50Hz - 230V
voltage
Operation
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
condition
Measuring
outdoor unit overall current with the current clamp meter at Power Cable.
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AW * Z24LBC
3.4
15[ C]
3.3
20[ C]
Indoor ambient Temp.
23[ C]
3.2
3.1
3.0
2.9
2.8
2.7
0
2
4
outdoor ambient temparature[ C]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AW * Z24LBC
12.0
11.5
11.0
10.5
10.0
9.5
9.0
0
2
4
outdoor ambient temparature[ C]
6
8
10
12
[50Hz-230V]
15[ C]
20[ C]
Indoor ambient Temp.
23[ C]
6
8
10
12
[50Hz-230V]
08-03
14
14