Outdoor Unit
2.4
Removal of
Procedure
Step
Disconnect the fan motor
connector S70.
1
Release the lead-wires
of the fan motor from
the groove of the
switch box.
2
The propeller fan can
be removed when the
washer faced nut (M8)
is removed.
3
Remove two screws for
removing the fan
motor. The lead wires
are disengaged by
raising the hooks which
fix the lead wires.
136
Propeller Fan
Warning Be sure to turn off all power supplies at least 10 min. before disassembling work.
Procedure
and
Fan Motor
Si06-305
Points
Remove the external plates
and the drip proof cover
protecting the electric parts.
Be sure to avoid forgetting to
restore the shelter and to
avoid losing or damaging it.
When restoring, match the M
mark of the propeller fan with
the D-cut of the motor shaft.
The fan should be restored
so that the mark
will be at
upper part of the fan motor.
Removal Procedure