Removal Of Propeller Fan And Fan Motor - Daikin D Series Service Manual

Non inverter pair, indoor/outdoor unit
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

Si01-501
3.4

Removal of Propeller Fan and Fan Motor

Procedure
Step
Disconnect the fan motor
connector S70.
The lead-wires of the
1
fan motor can be
disengaged by passing
through the clearance
between the heat
exchanger and the
switch box.
The propeller fan can
2
be removed when the
washer faced nut
(M8) is removed.
3
Remove two screws for
removing the fan motor.
The lead wires are
disengaged by raising
the hooks which fix the
lead wires.
Remove the fan motor.
4
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
R25/35DV1
Points
Remove the external plates
and the drip proof cover
protecting the electric parts.
Be sure to avoid forgetting to
restore the shelter and to
avoid losing or damaging it.
When restoring, match the
mark of the propeller fan with
the D-cut of the motor shaft.
The fan should be restored
so that the mark
will be at
upper part of the fan motor.
199

Hide quick links:

Advertisement

Table of Contents
loading