Connecting a burner

Pressure jet oil/gas burner
The burner cables are included in the
standard boiler delivery.
Connect the burner according to DIN
4791 [or local regulations].
B
fA
STB
TR
L1
N T1 T2 S3 B4
M
A To the control unit
M To the burner
Burner without plug
Install the mating plug from Viessmann
or from the burner manufacturer; con-
nect the burner cable.
Atmospheric burner
The burner cables are included in the
standard boiler delivery.
Installation sequence
Max. current drawn 4 (2) A.
Terminal markings
L1
Phase via high limit safety cut-
out to the burner
PE
Earth conductor to burner
N
Neutral conductor to burner
T1, T2 Control chain
S3
Burner fault terminal
B4
Hours run meter terminal
Signal pass direction:
Control unit → burner
Signal pass direction:
Burner → control unit
Equipment codes
STB Control unit high limit safety cut-
out
TR
Control unit thermostat
H1
Burner fault signal
BZ
Hours run meter
Max. current drawn 4 (2) A.