Minimum Clearances; Electrical Data - Carrier AQUASNAP JUNIOR 30RHV Installation Manual

Air-cooled water refrigerating unit assembly
Table of Contents

Advertisement

30RHV

Minimum clearances

B
Mod.
A
mm
B
mm
C
mm
D
mm
E
mm
F
mm
Table III: Electrical data
Unit
Power supply
Locked rotor amps
Full load amps
Delayed fuses (class gL)
power supply protection
Section of the power
supply conductors
Delayed fuses (class gL)
auxiliary circuit protection
Compressor
Capacitor
Fan motor (230-1-50)
Current input
Capacitor
Compressor crankcase
heater (230-1-50)
Current input
A
C
A
F
30RHV 006 - 008 - 011
100
250
500
100
670
400
006
008
V - ph - Hz
230-1-50
230-1-50
LRA
58
82
FLA
16
19
A
20
25
mm
2
3 x 2,5
3 x 4,0
A
4
4
µF/V
40/450
50/450
A
0,82
1,1
µF/V
4/450
3/450
W
25
25
A
0.11
0.11
30RHV
011
230-1-50
400-3-50
97
48
23
10
30
12
3 x 4,0
5 x 2,5
4
4
60/450
1,64
1,64
4/450
4/450
Note:
The main supply connecting cable must be H07 RN-F (or
higher) type, synthetic rubber insulation with Neoprene
coating, according to EN 60335-1 codes.
25
25
Interlocks with the pumps or other accessories have to be
0.11
0.11
inserted as shown in the notes on the wiring diagram.