38BC / 38BH
Minimum clearances
B
F
Table III: Operating limits
Cooling (2)
Heating (3)
Mains power supply
Notes:
1. Data referred to the outdoor unit only.
2. According to ISO 5151.2/T1.
3. According to ISO 5151.2/High+.
4. Units 38BCS 012 and 014 are provided with head pressure
control suitable up to –10°C ambient temperature
(38BCS009 up to –5°C).
d.b. - dry bulb;
w.b. - wet bulb
System charge
Refrigerant Suitable up to Extra charge
Size
Cooling only
007
Cooling only
009
Cooling only
012
Cooling only
014
Heat pump
007
Heat pump
009
Heat pump
012
Heat pump
014
R-410A
A
C
A
Model
A mm
B mm
C mm
D mm
E mm
F mm
(1)
Maximum conditions
Minimum conditions
Maximum conditions
Minimum conditions
Nominal single-phase voltage
Operating voltage limits
charge (g)
m
630
10
660
10
730
10
980
10
630
10
820
10
940
10
920
10
007-009-012-014
50
100
400
50
300
400
outdoor temperature 43°C
indoor temperature 32°C d.b.; 23°C w.b.
outdoor temperature 15°C
indoor temperature 21°C d.b.; 15°C w.b.
outdoor temperature 24°C d.b.; 18°C w.b.
indoor temperature 27°C d.b.
outdoor temperature –10°C d.b.
230V ~ 50Hz
min. 198V – max. 264V
WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures.
In these cycles, fan speed will automatically reduce and cannot be
varied until defrost cycle is completed.
Extra charge (g)
g/m
with indoor unit 42VMC with indoor unit 40SMC
25
–
25
–
25
–
25
100
25
–
25
–
25
–
25
150
E N G L I S H
D
E
E
D
F
(4)
Extra charge (g)
–
–
50
–
–
–
50
–
GB - 3