Minimum Clearances And Operating Limits - Carrier 42PQV...S Installation Manual

Table of Contents

Advertisement

42PQV...S/38VBH...S

Minimum clearances and operating limits

100
min.
B
Table III: Operating limits
Cooling
Heating
Mains power supply
Notes:
1. Data referred to the outdoor unit only.
d.b. - dry bulb;
w.b. - wet bulb
GB - 4
90
min.
1900
min.
A
C
A
Model
A mm
B mm
C mm
D mm
E mm
F mm
(1)
Maximum conditions
Minimum conditions
Maximum conditions
Minimum conditions
Nominal single-phase voltage
Operating voltage limits
200
min.
009-012
50
100
400
50
300
400
outdoor temperature 43°C
indoor temperature 32°C d.b.; 23°C w.b.
outdoor temperature 15°C
indoor temperature 21°C d.b.; 15°C w.b.
outdoor temperature 24°C d.b.; 18°C w.b.
indoor temperature 27°C d.b.
outdoor temperature –10°C d.b.
220V-240V, 50/60Hz
min. 198V – max. 264V
WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures. In these cycles, fan speed will automatically stop,
louvre(flap) will be fixed at horizontal position and cannot be varied until
defrost cycle is completed.