Indoor Unit Pcb Abnormality - Daikin FTXG-J Service Manual

Wall mounted type j-series
Hide thumbs Also See for FTXG-J:
Table of Contents

Advertisement

SiBE041012_B
4.2

Indoor Unit PCB Abnormality

A1
Error Code
Method of Error
The system checks if the circuit works properly within the microcomputer of the indoor unit.
Detection
Error Decision
The system cannot set the internal settings.
Conditions
Supposed
Causes
Troubleshooting
Note:
Check the following connector.
Wall mounted type
Service Diagnosis
Wrong models interconnected
Defective indoor unit PCB
Disconnection of connector
Reduction of power supply voltage
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the combination of the
indoor and outdoor unit.
OK?
YES
Check the connection of
connectors (See Note.).
OK?
NO
Correct the connection.
Error repeats?
NO
Model Type
Terminal board ~ Control PCB (H1, H2, H3)
NO
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
YES
Check the power supply
voltage.
Voltage as rated?
YES
Start operation.
Error repeats?
NO
YES
Check the power supply
voltage.
Voltage as rated?
YES
Start operation.
Error repeats?
NO
Connector
Troubleshooting
Match the compatible
models.
NO
Correct the power
supply.
YES
Replace the indoor unit
PCB (1).
Completed.
NO
Correct the power
supply.
YES
Replace the indoor unit
PCB (1).
Completed.
Completed.
(R15270)
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents