Four Way Valve Abnormality - Daikin FTXG-J Service Manual

Wall mounted type j-series
Hide thumbs Also See for FTXG-J:
Table of Contents

Advertisement

SiBE041012_B

4.17 Four Way Valve Abnormality

EA
Error Code
Method of Error
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Detection
Error Decision
A following condition continues over 1 ~ 10 minutes (depending on the model) after operating
for 5 ~ 10 minutes (depending on the model).
Conditions
Supposed
Causes
Service Diagnosis
Cooling / Dry
(room thermistor temp. – indoor heat exchanger temp.) < –5°C
Heating
(indoor heat exchanger temp. – room thermistor temp.) < –5°C
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Troubleshooting