Facility Setting Jumper (Cooling At Low Outdoor Temperature) - Daikin FTXG-J Service Manual

Wall mounted type j-series
Hide thumbs Also See for FTXG-J:
Table of Contents

Advertisement

SiBE041012_B
4.3
Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
RXG50K3V1B
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail
You can expand the operation range to –10°C by cutting jumper J6 on the outdoor unit PCB. If
the outdoor temperature falls to –18°C or lower, the operation stops. If the outdoor temperature
rises, the operation starts again.
Caution
1. If the outdoor unit is installed where the outdoor heat exchanger of the unit is exposed to
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
4. Cutting jumper sets the indoor fan tap to the highest position.
5. Replace the PCB if you accidentally cut a wrong jumper.
Trial Operation and Field Settings
direct wind, provide a windbreak wall.
off when using facility settings.
settings are being used.
A humidifier might cause dew condensation from the indoor unit outlet vent.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Field Settings
Cut the jumper J6.
(R18276)
129