Daikin FDM10CXV1 Technical Manual page 123

Table of Contents

Advertisement

Model: FDYB50CXV1 - RY50DXY1
Heating Mode
ID DB
-9°C
TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
15°C
8.814
8.814
10.164 10.164 10.614 10.614 15.565 15.565 18.266 18.266 19.617 19.617 20.967 20.967
17°C
8.807
8.807
10.025 10.025 10.431 10.431 15.555 15.555 17.778 17.778 19.075 19.075 20.371 20.371
19°C
8.799
8.799
21°C
8.792
8.792
23°C
8.572
8.572
25°C
8.351
8.351
27°C
8.131
8.131
Remark:
AFR: Air fl ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2.
shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
-6°C
-5°C
9.886
9.886
10.248 10.248 15.544 15.544 17.290 17.290 18.533 18.533 19.775 19.775
9.747
9.747
10.065 10.065 15.533 15.533 16.802 16.802 17.991 17.991 19.180 19.180
9.555
9.555
9.883
9.883
9.363
9.363
9.700
9.700
9.170
9.170
9.517
9.517
Frost Region
Outdoor WB
6°C
12°C
14.764 14.764 16.314 16.314 17.449 17.449 18.584 18.584
13.994 13.994 15.826 15.826 16.907 16.907 17.988 17.988
13.225 13.225 15.338 15.338 16.365 16.365 17.392 17.392
Performance Data
15°C
18°C
120

Hide quick links:

Advertisement

Table of Contents
loading