Installation Of Indoor Unit - McQuay RCM20D Installation Manual

Table of Contents

Advertisement

PRELIMINARY SITE SURVEY
Electrical supply and installation shall conform to the
local authority (e.g. National Electrical Board).
Voltage supply fluctuation must not exceed ±10% of the
rated voltage. Electricity supply lines must be
independent of welding transformers which can cause
high supply fluctuation.
Ensure that the installation location is convenient for
wiring and piping.
FIGURE A
FIGURE B
Please ensure that the following steps are taken:
Check the gradient for drainage flow as recommended
in Figure B.
Provide clearance for easy servicing and optimal air flow
as shown in Figure C.
INSTALLATION OF THE INDOOR UNIT
1-5
STANDARD MOUNTING
Ensure that the overhead supports are strong enough to hold
the weight of the unit. Position the hanger rods (wall
mounting bracket for floor standing), and check for its
alignment with the unit as shown in Figure A. Also, check
that the hangers are secured and the base of the fan coil unit
is leveled in both horizontal directions, taking into account
the gradient for drainage flow as recommended in Figure B.
MODEL
20
25
A
1214
1214
B
666
666
C
273
273
D
130
130
E
1160
1160
F
27
27
G
77
77
H
745
745
I
25
25
J
209
209
K
486
486
L
108
108
M
360
360
Note: Floor standing installation available for CE20D/DR
and CE25D/DR only.
The indoor unit must be installed such that there is no
short circuit of the cool discharge air with the warm
return air.
Do not install the indoor unit where there is direct
sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit
must be a large distance away from the door.
30
40
50
1214
1714
1714
666
666
666
273
273
273
130
130
130
1160
1560
1560
27
27
27
77
77
77
745
1235
1235
25
25
25
209
331
331
486
486
486
108
108
108
360
600
600