NOTE: The LCD temperature display may not agree with the temperature reading of your pool or spa ther-
mometer. The heater reads the water temperature at the inlet. Due to the circulation characteristics of any pool
or spa, the water temperature at the inlet to the heater may differ from that observed at a given location in the
pool or spa.

STATUS AND DIAGNOSTICS

The digital thermostat models are programmed to display a variety of status and diagnostic messages, depend-
ing on the operating conditions.
The following heat status messages are displayed in
Pool, Spa, and Remote modes when there are no
active fault conditions.
Display
Call for heat established, flame
Heating
present
Spark
Spark operating
No Demand
Heat demand is satisfied
The following conditions are displayed in Pool, Spa
and Remote modes.
Display
Sensor
Thermistor temperatures disagree
Failure
by more than 2°F
Thermistor sensor failed open.
Sensor Open
(Below -20°F)
Thermistor sensor failed short.
Sensor Short
(Above 217°F)
Board is sensing flame when both
Flame w/o
main and pilot valves are command-
CFH
ed shut.
PV Output
Pilot gas valve output is not in com-
Fault
manded state.
MV Output
Main gas valve output is not in com-
Fault
manded state.
Voltage is sensed at the Lo NOx ter-
LoNox Tab
minal on a non-Lo NOx heater (Lo
Fault
NOx tab is intact).
Internal Fault Board fault, replace board.
EEPROM
Memory fault, reset set points,
Fault
replace board if fault does not clear.
Clock/
Time clock/fireman switch circuit is
Fireman Sw
open.
Low Temp
Water temperature below 36°F.
Lockout
Condition
Condition
The following conditions are displayed only while there
is a demand for heat present.
Display
Water Sw
Water pressure switch open.
Open
Vent/Field
Vent spill switch/field switch #1
Sw #1
open.
Hi Limit 1
High limit 1 open.
Fault
Hi Limit 2
High limit 2 open.
Fault
Rollout Sw
Rollout switch open.
Open
Flow/Field
Flow switch/field switch #2 open.
SW #2
3 fan switch faults within same heat
Fan Lockout
demand cycle, power must be
cycled to clear the fault.
Heater shut down for 5 minutes
Fan 5 Min
because LoNox fan switch didn't
Delay
close.
Alternating
sensed" - Pilot flame not estab-
Ignition
lished within the required time (15
Lockout
sec or 90 sec).
(Propane Tab
Alternating
Broken)
Failure" - Pilot flame lost during the
8 second trial to ignite the main
burner.
Ignition
Alternating
Failure
sensed" - Pilot flame not estab-
(Propane Tab
lished within 90 seconds.
Not Broken)
Alternating
Ign 6min
Failure" - Pilot flame lost 4 times
Delay
within the 8 second trial to ignite the
(Propane Tab
main burner. Heater will lockout for
Not Broken)
6 minutes before retrying.
39
Condition
with
"No
pilot
with
"Main
Ign
with
"No
pilot
with
"Main
Ign