PYROTECH FLUE TERMINATION (COWLS) REGULATIONS
Natural Draft
Refer to Note 1
AREA
Horizontally from a neighboring structure. ......................................................1000mm
A:
If less than a meter horizontally from a neighboring structure
B:
then terminates above that structure by. ...........................................................500mm
From any opening into a building....................................................................1500mm
C:
From another flue terminal. ................................................................................200mm
D:
Notes:
1.
A trafficable roof designed for personal or public use, the end of the flue shall be at least 2
meters above the roof level. This dimension is to be increased where necessary so that
the minimum distance of 500mm is maintained above any surrounding parapet or at least
200mm from the nearest part of a chimney.
2.
The current version of the AS5601-2004 gas codes and any other relevant codes should
be read in conjunction with the above guidelines to ensure a correct and safe installation.
D
B
A OR B
C
Refer to Note 1
500mm
CLEARANCE REQUIRED
500mm
31