Electrical Connection - Miele G 7782 Operating Instructions Manual

Washer/disinfector
Table of Contents

Advertisement

Electrical connection

IMPORTANT: All electrical work must
be carried out by a qualified electrician
and in compliance with all local and na-
tional electrical codes.
Before making any connections, check
that the voltage shown on the data
plate corresponds to your power sup-
ply. Data plate is located on back of
unit and behind service panel.
The washer/disinfector is supplied as
standard for connection to a 208 V,
60 Hz, single phase power supply and
is fitted with a power supply cord 6 ft
(1.8 m) long with a cross-section of
AWG 10-4. Connect washer/disinfector
to the main power supply (junction box
or electrical cord to outlet) according to
the opposite chart.
NOTE: If an electrical cord is used,
make sure cord is the proper size and
voltage/current rating for the washer/
disinfector as identified on the data
plate.
Voltage:
Frequency:
Rated load:
Circuit breaker:
The washer/disinfector can be con-
verted for connection to a 3-phase
power supply.
WARNING - ELECTRICAL SHOCK
HAZARD: Washer/disinfector must
be correctly grounded!
14
208 V, single phase
60 Hz
6.0 kW
30 A per phase
The wiring diagram can be found be-
hind the kickplate on the left hand side,
attached to the floor of the machine.
The data plate with serial and model
numbers is on the rear of the machine
and on the kickplate behind the service
panel.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents