Trianco EuroStar WM 50 User, Installation, Commissioning & Servicing Instructions
Trianco EuroStar WM 50 User, Installation, Commissioning & Servicing Instructions

Trianco EuroStar WM 50 User, Installation, Commissioning & Servicing Instructions

Advertisement

TRIANCO
EuroStar WM 50/65
In The Wall Boiler
OIL FIRED CENTRAL HEATING BOILERS
BED 92/42 EEC
EMC 89/336 EEC
USER, INSTALLATION
COMMISSIONING & SERVICING
BALANCED FLUE
INSTRUCTIONS
To be retained by householder

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EuroStar WM 50 and is the answer not in the manual?

Questions and answers

Summary of Contents for Trianco EuroStar WM 50

  • Page 1 TRIANCO EuroStar WM 50/65 In The Wall Boiler BALANCED FLUE OIL FIRED CENTRAL HEATING BOILERS BED 92/42 EEC EMC 89/336 EEC USER, INSTALLATION COMMISSIONING & SERVICING INSTRUCTIONS To be retained by householder...
  • Page 2 HEALTH AND SAFETY INFORMATION FOR THE INSTALLER AND SERVICE ENGINEERS Under the Consumer Protection Act 1987 and the Health and Safety at Work Act 1974, it is a requirement to provide information on substances hazardous to health (COSHH Regulations 1988). The Company takes every reasonable care to ensure that these products are designed and con- structed to meet these general safety requirements, when properly used and installed.
  • Page 3: Table Of Contents

    CONTENTS PAGE 1. USER INSTRUCTIONS After sales service information 2. INTRODUCTION 3. TECHNICAL INFORMATION 4. INSTALLATION Regulations Health and Safety Siting the Boiler 5. OIL SUPPLY Oil storage tank - Steel and Plastic Oil supply line Single pipe oil supply Two pipe oil supply Oil De-aerator - Single pipe supply 6.
  • Page 4: User Instructions

    82° C (high) to 55° C (low). The Trianco EuroStar WM 50/65 In The Wall Boilers have been designed and constructed to give years of trouble Set the temperature by turning the knob to the required free service and these instructions are provided to assist temperature.
  • Page 5 TIME-SWITCH PROGRAMMER otherwise sludge and water could be sucked into the oil pipe to affect the burner’s operation and reduce pump life. When choosing the operating times for your boiler, it is After a delivery of oil, it is recommended that the oil is useful to remember that central heating usually takes allowed to settle in the tank for about half an hour before between half an hour before is becomes effective.
  • Page 6: After Sales Service Information

    Where the appliance falls outside the 12 month unavailable? guarantee period (see terms and conditions enclosed). Step 3: Contact Trianco Direct. We will provide you with the name and telephone number of our Service • The appliance has not been correctly installed, Agent.
  • Page 7: Introduction

    Building Regulations, Part L. Failure to meet the terms of these requirements may invalidate your guarantee. The Trianco EuroStar WM 50/65 In The Wall Boilers have been designed to conform to European Directive/Standards BED 92/42 EEC, LVD EN 60335-1 EMC 89/336/EEC THE PERSON(S) WHO INSTALLS THIS APPLIANCE, COMMISSIONS, SERVICES OR CARRIES OUT ANY REMEDIAL WORK, I.E.
  • Page 8: Technical Information

    3 TECHNICAL INFORMATION Technical Specifications EuroStar Boiler Models WM 50 WM65 Rated Input (Btu/h) 56,200 73,610 (kW) 16.4 21.6 Rated Output (Btu/h) 50,000 65,800 (kW) 14.7 Oil Burner Model See burner details leaflet See burner details leaflet Weight (empty) (kg) (lb) Water content (litre)
  • Page 9: Installation

    4. INSTALLATION Clearance and Service Access When siting the boiler, ensure adequate clearance is Regulation allowed internally and externally for future servicing. Installation of the boiler must comply with the following British Standards and Unpacking the Boiler Regulations: a) Remove the front door (white painted) and move to BS 5410: Part 1 - Code of Practice for Oil Firing a safe place to avoid damage.
  • Page 10 When locating the boiler, care should be taken in respect Insert external duct over internal duct, holes to bottom. of the flue terminal which should be within the parameters Adjust from wall thickness ensuring a minimum of laid down within Fig 3 40mm from wall face to front of sleeve;...
  • Page 11 Important: External The isolating valve should be fitted on the flow pipe (see Baffles should be re-fitted ensuring correct position of oil line details, Fig 4) Fire valve sensing phial should be baffle prior to inserting baffle cassette which is retained located into clip provided above burner.
  • Page 12: Oil Supply

    5 OIL SUPPLY Fire Valve a fire-valve must be fitted in the oil line outside the building with its sensing phial positioned within the burner compartments. clip is provided for retaining the phial The oil burner is factory set to burn 28 sec. Kerosene to above the burner.
  • Page 13 FIG. 7 SINGLE PIPE OIL SUPPLY INSTALLATION...
  • Page 14 FIG. 5 TWO PIPE OIL SUPPLY INSTALLATION...
  • Page 15 FIG. 6 DE-AERATED OIL SUPPLY INSTALLATION...
  • Page 16: Electrical

    6. ELECTRICAL secure it in position. The control panel front can now be secured in position using the two self tapping screws provided. Electrical Supply 230V 1 Phase 50 Hz (Fused 5 Amp) The thermostats are identified as follows:- NOTE: Boiler thermostat Green THIS APPLIANCE MUST BE EARTHED...
  • Page 17 FIG. 9 BOILER WIRING DIAGRAM...
  • Page 19: Servicing

    7. SERVICING To maintain the boiler’s high thermal efficiency and 12) Prior to replacing burner remove cap form oil pump reliable operation, it should be serviced annually by a (4 x 4 mm allen screws), clean filter and reassemble. qualified engineer preferable OFTEC trained and Note: we recommend the burner be fitted after the registered.
  • Page 20: Commissioning

    8. COMMISSIONING It is the responsibility of the installer to ensure the boiler Cycle the burner two or three times until the flame is properly commissioned, failure to do so will make the cuts off sharply - this indicates any remaining air has boiler’s guarantee and any extended warranty null and been dispersed.
  • Page 21: Fault Finding

    9. FAULT FINDING ELECTRICITY SAFETY - Before making any electrical checks, it is recommended that the safe isolation of electrical supplies procedure are followed. FAULT POSSIBLE CAUSE ACTION BURNER FAILS TO START Is there power to the boiler Check 5 AMP fuse NB, THIS BOILER IS FITTED WITH A POWER BREAKER (RCD) UNIT, IF THE UNIT TRIPS AFTER RE-SETTING, ISOLATE AND CHECK FOR SHORT CIRCUIT WIRING.
  • Page 22: Fault Finding

    FAULT FINDING (Cont’d) FAULT POSSIBLE CAUSE ACTION POOR FLAME CUT-OFF Air in pump or at back of nozzle Bleed pump through pressure gauge port, also check for leaks in oil line if 2-pipe system. Oil contaminated with water Run off oil at burner until free of water and drain condensation from tank.
  • Page 23: Spares

    10 SPARES Item Description No. Off Part No. Boiler Body WV - Painted - 65,000 209610 Top Front & Bottom Insulation 209695 Door Casing Assembly 222361 Boiler Casing Assembly 222366 Boiler Mounting Plate Assembly 209710 Inner Duct Assembly 209701 Fascia Panel Assembly 222363 Acoustic Cassette Assembly 209630...
  • Page 24 13 14 15 FIG. 12 17 18 FIG. 13 FIG. 14...
  • Page 25 ADDITIONAL BRACKET FITTING INSTRUCTIONS Additional bracket for fixing mounting plate to wall is required, should the cut- out have been made too large. 2 off/per See drawing 209717 (contained in screw pack) 91437 No 12 X 50 SCREW (contained in screw pack)
  • Page 26 DECOR PANEL FITTING INSTRUCTIONS (this item is available as an optional extra) Fig 1 of the cupboard door if the boiler is fitted flush with the 1. To fit decor panel to existing cupboard door firstly top of the cupboards. remove boiler door casing as this is not required.
  • Page 27 FUNCTIONAL FLOW DIAGRAM FUSED SPUR 5 AMP EXTERNAL CONTROLS FROST THERMOSTAT TRIP SERVICE SWITCH CENTRE OFF PROG • • • BOILER THERMOSTAT LIMIT GREEN LIGHT THERMOSTAT MAINS ON BURNER...
  • Page 28 Fax: (0114) 245 1419 www.trianco.co.uk © Trianco Limited, Copyright in this brochure and the drawings or illustrations contained in it is vested in Trianco Limited and neither the brochure or any part thereof may be reproduced without prior written consent.