Required Tools
• digital voltmeter
• small phillips & flat-blade screwdrivers
• pliers
• 1/16" hex wrench
• key hole saw
Mounting
CTE–5100 series thermostats may be mounted horizontally or vertically to a standard 2" x 4" (51 x 102)
handy box using a HMO-5024/26 or 5030/5031 backplate, or directly to a hollow wall using drywall bracket
HMO-5023.
Mount thermostats on walls unaffected by sunlight or drafts to ensure accurate average
temperature sensing. All CTE–5100 series thermostats require a scale plate and a cover which must be
ordered separately.
Electrical Box Mounting
1. Install, but DO NOT TIGHTEN, the HMO-5024/26 or 5030/5031
backplate to a handy box using the two 6-32 screws (included).
2. Adjust and level the backplate using the slotted mounting hole.
3. Tighten the two mounting screws.
4. Pull all thermostat wires and cable through the backplate and
decorative trim plate opening (included with HMO-5024/5026 or
5030/5031). Be careful not to damage the trim plate while wiring.
5. Connect the thermostat's wires according to it's particular
application. Refer to project drawing or the wiring chart.
6. Position the trim plate between the backplate and the thermostat
(cover removed).
7. Align the mounting holes and secure the assembly with the two
6-32 x 2" self-tapping screws (included).
Hollow Wall Mounting
Thermostats may be mounted on a hollow wall up to 5/8" thick using the HMO–5023 Drywall Mounting Kit.
1. Using the template, cut a 1–1/2" x 2–11/16" opening in the drywall.
2. Loosely mount the HMO–5023 bracket to the thermostat (cover removed) using the two 6-32 x 2" screws.
3. Pull all thermostat wires or cable through the bracket's 'wiring/cable access hole.
4. Connect the thermostat wires according to it's particular application. Refer to the project drawing or the
wiring chart.
5. Insert bracket diagonally, through the wall opening, center and tighten screws.

Installation Guide

Electronic Room Thermostats
CTE–5101, 5102, 5103, 5104, 5105
HMO-5024/26 or 5030/5031
HMO–5023 Drywall Mounting Kit
Back Plate

Advertisement

loading

Summary of Contents for KMC Controls CTE–5101

  • Page 1: Installation Guide

    Electronic Room Thermostats CTE–5101, 5102, 5103, 5104, 5105 Installation Guide Required Tools • digital voltmeter • small phillips & flat-blade screwdrivers • pliers • 1/16" hex wrench • key hole saw Mounting CTE–5100 series thermostats may be mounted horizontally or vertically to a standard 2" x 4" (51 x 102) handy box using a HMO-5024/26 or 5030/5031 backplate, or directly to a hollow wall using drywall bracket HMO-5023.
  • Page 2 Mounting Continued Setpoint Stops Setpoints can be locked, or limited, using setpoint stops. Each HFO–0027 Setpoint Stop Strip (accessory sold separately) contains four stops. 1. Break a stop from the strip by gently folding on the seam with pliers. 2. Insert a stop into the slider track on one or both sides of the slider. 3.
  • Page 3 Adjustments and Calibration Thermal calibration is not required . Minimum and maximum control points can be calibrated before or after the thermostat has been installed. Adjusting the thermostat: 1. Using 1/16" hex/key, turn the setscrews on each side of the unit clockwise until the cover loosens. 2.
  • Page 4 Maintenance No routine maintenance is required. Each component is designed for dependable, long term reliability and performance. Careful installation will also ensure long term reliability and performance. KMC Controls P.O. Box 497 19476 Industrial Drive New Paris, IN 46553 U.S.A.

This manual is also suitable for:

Cte-5102Cte-5103Cte-5104Cte-5105