Wired Remote Control Local Setting Mode - Panasonic S-22KA1E5 Service Manual

Hide thumbs Also See for S-22KA1E5:
Table of Contents

Advertisement

17.5

Wired Remote Control Local Setting Mode

• During unit off, press the TEST RUN button for 5 seconds to enter LOCAL MODE.
• Press Temperature Up / Down button to select Mode No.
• Press Timer SELECT button to enter setting mode.
• Press Timer Up / Down button to select setting value.
• Press Timer SET button to confirm the selection.
• Press TEST RUN button to exit LOCAL SETTING MODE. If no operation is performed for 30 seconds, exit
LOCAL SETTING MODE.
Mode
Items
No.
00
Centralized control address
01
Fan speed up
Nighttime low noise
02
Nighttime low noise ON time
Nighttime low noise OFF time
Thermostat OFF
03
indoor fan control
Thermostat OFF
04
point adjustment
06
Outdoor unit address
10
Group address reset
11
Thermistor selection
12
Ventilation unit control
Note 1) Mark
in the column of the "Individual setting" shows a setting item individually made for each connected
indoor unit.
Note 2) "R" represents remote control and I "indoor unit".
Note 3) Start the setting from the setting value 000.
17.5.1 Fan Speed Up
This control can increase the fan speed of indoor unit with DC motor.
When enable, the HIGH fan speed setting at Remote Control, indoor unit fan tap changed from Hi to SHi.
Setting value
000 – 200: Address 0 – Address 200
000: OFF
000: Execute Reset
(Level 0)
001 – 003: Level 1 – Level 3
0:00 23.50 (10 minutes interval)
0:00 23.50 (10 minutes interval)
000: Default control
001: 10 seconds fan sampling operation
002: Fixed fan speed operation
000: default Thermostat OFF point (ΔD)
001: Cool = ΔD+2°C, Heat = ΔD-2°C
002: Cool = ΔD+4°C, Heat = ΔD-4°C
003: Cool = ΔD-2°C, Heat = ΔD+2°C
004: Cool = ΔD-4°C, Heat = ΔD+4°C
000: Clear address
001 – 199: Address 1 - Address 199
000: Non-processed
001: Execute Reset
000: Non-processed
001: Remote control
000: OFF
002: ON
(OFF coupling)
105
Individual
Setting
Note 1)
001: ON
001: ON
(no-interlocking)
003: ON
(ON/OFF coupling)
Setting
value
memory
terminal
Note 2)
I
I
R
I
I
I
Note 3)
R
R